To configure the power monitoring through the H831PMU (backup power using the Fe-lithium
battery) with such configurations, do as follows:
huawei(config)#
emu add 3 H831PMU 0 0 RS485
huawei(config)#
interface emu 3
huawei(config-if-h831pmu-3)#
power supply-parameter 59 48
Send command to environment monitor board ,please waiting for the ack
huawei(config-if-h831pmu-3)#
Execute command successful
huawei(config-if-h831pmu-3)#
quit
huawei(config)#
emu add 4 liBATTERY 0 23 rs485 battery1
huawei(config)#
interface emu 4
huawei(config-if-libattery-4)#
power batteryinstall 2010-08-20
huawei(config-if-libattery-4)#
display power run info
EMU ID: 4 LiBattery run information
----------------------------------------------------------------------------
Battery charge state: Charge
Battery voltage: 54.01V
Battery current: 0.82A
Battery temperature: 29°C
Battery capacity specification: 10A
Battery capacity remained percentage: 97%
Battery charge or discharge number: 13
The sum of discharge capacity: 106Ah
----------------------------------------------------------------------------
huawei(config-if-libattery-4)#
quit
huawei(config)#
save
3.15.3 Configuring the Monitoring Through the Fan
This topic describes how to configure the speed adjustment mode and the alarm function of the
fan. Thus, the fan speed of the MA5616 can be adjusted automatically, and the fan tray of the
MA5616 can be monitored.
Context
The fan tray requires the RS-232 serial port for data communication.
The subnode ID of the fan tray is invariably 2.
Procedure
Step 1
Add an EMU.
Run the
emu add
command to add an EMU.
Step 2
Configure the speed adjustment mode of the fan.
Run the
fan speed
command to configure the speed adjustment mode of the fan. By default, the
fan speed adjustment mode is automatic.
NOTE
When the fan speed adjustment mode is the manual mode, you can run the
fan speed adjust
command to set
the fan speed. The speed level can be 0, 1, 2, 3, 4, or 5. Here, 5 stands for the highest level, and 0 stands for the
lowest level.
Step 3
Configure whether alarms associated with the fan tray are reported.
Run the
fan alarmset
command to configure the reporting of alarms related to the fan tray.
Step 4
Query the configuration parameters of the fan tray.
SmartAX MA5616 Multi-service Access Module
Configuration Guide
3 Basic Configuration
Issue 04 (2011-10-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
151