5.5.6 Installing a Riser Card
This topic describes how to install a riser card.
Scenarios
Install a riser card if:
●
A riser card has failed.
●
A PCIe card on the riser card has failed.
Prerequisites
Conditions
●
You have powered off the RH8100 V3. For details, see
. Then you have removed all power cables from the server.
●
You have removed the front I/O module from the RH8100 V3. For details, see
5.5.1 Removing the Front I/O Module
.
●
You have installed all PCIe cards on the riser card. For details, see
Data
●
You have obtained the cabinet number and chassis number of the RH8100 V3.
●
You have located the RH8100 V3 based on the preceding information, and
labeled its panel to prevent misoperations.
●
You have determined the position on the RH8100 V3 for installing a riser card.
Tools
●
ESD gloves
●
Packaging materials, for example, an ESD bag
●
M3 Phillips screwdriver
Hardware
Spare riser card
Procedure
Step 1 Wear an ESD wrist strap or ESD gloves. For details, see
.
Step 2 Take the spare riser card out of the ESD bag, and install all PCIe cards of the
required model on the riser card.
Step 3 Insert the riser card into the slot on the front I/O module. See step (1) in
.
Step 4 Press the ejector lever as far as it will go. See step (2) in
.
Step 5 Tighten the screws on the riser card. See step (3) in
.
RH8100 V3 Server
User Guide
5 Removing and Installing Parts of the RH8100 V3