(Downflow) Connect a pressure tube to the
+
mark on the differential pressure switch and
route the pressure tube to the top of the NetCol8000-C. Connect a pressure tube to the
–
mark
on the differential pressure switch and route the pressure tube to the bottom of the
NetCol8000-C. (Upflow) Connect the hose to the
–
mark on the pressure differential sensor.
Step 7
After powering on the device, tap
Start
on the LCD home screen, choose
Settings
>
Alarm
Settings
>
Main Board
, and check whether
Air filter blocked
is set to
Allow
.
Step 8
Choose
Maint
>
Diagnostic Mode
>
Enter
and set
Indoor fan
to 100%.
Step 9
Block almost 100% air volume at the return air side using a plastic foam board or baffle plate,
and check whether the Air filter blocked alarm is generated. If the alarm is generated, the
differential pressure switch works properly. Then exit the diagnostics mode.
----End
6.7.4 Replacing a T/H sensor
Procedure
Step 1
Tap
Shutdown
on the LCD home screen.
Exercise caution because the device is still energized when it is shut down over the LCD.
Step 2
Open the front door.
Step 3
Disconnect cables from the RS485_IN and RS485_OUT ports on the T/H sensor.
Step 4
Pull out the T/H sensor in the direction.