6 System Operation and Maintenance
Issue 06 (2020-01-13)
Copyright © Huawei Technologies Co., Ltd.
171
6.4 Annual Maintenance
Table 6-3
Annual maintenance
Maintenanc
e Item
Operation
Troubleshooting
T/H sensors
Check that the
temperature and
humidity readings are
correct as measured.
If the temperature deviation is greater than
1°C or humidity deviation is greater than 5%,
calibrate or replace the humidity and
temperature sensor. For the calibration
method.
Heat
exchanger
Check that no foreign
matter exists on the heat
exchanger surface.
Remove foreign matter.
6.5 Alarm References
Table 6-4
Alarm description (V200R001 software version)
Alar
m ID
Alarm
Name
Alarm
Severi
ty
Impact
Possible Cause
Solution
a001
Return air
1/2/3/4 temp
invalid
Major
An alarm is
triggered.
1.
The cables to the
temperature sensor are
loose or damaged.
2.
The temperature sensor is
faulty.
1.
Check the cables to
the temperature
sensor.
2.
Maintain or replace
the temperature
sensor.
Fresh air
temperature
invalid
Return air
damper
temp invalid
a002
Return air
high
temperature
alarm
Critical An alarm is
triggered.
1.
The temperature sensors or
temperature and humidity
sensors are located in
inappropriate positions.
2.
The thermal load power is
high or the cooling capacity
is insufficient.
3.
The ambient temperature
exceeds the upper
threshold.
1.
Adjust the positions of
the temperature
sensors or temperature
and humidity sensors.
2.
Add smart cooling
products or contact
Huawei technical
support.
3.
Measure the ambient
temperature. Check
whether other causes