Table 3-5 Cable specifications
Application
Scenario
Specifications
Remarks
Indoor unit
power cable
(optional)
Electrical power cable, 600 V/1000 V,
ZA-RVV, 5 x 6 mm
2
, black (five core
wires), 46 A, outdoor cable, CE
Cable should not
be lighter than
normal PVC
sheathed flexible
cord (IEC 60227
53). The length is
determined by site
survey.
Naked crimping terminal: OT, 6 mm
2
,
M6, 50 A, tin plating, 12-8 AWG
Delivered with the
fittings
Outdoor unit
power cable
(optional)
Electrical power cable, 600 V/1000 V,
ZA-RVV, 3 x 6 mm
2
, black (three core
wires), 46 A, outdoor cable, CE
Cable should not
be lighter than
chloroprene rubber
armored flexible
cord (IEC 60245
57). The length is
determined by site
survey.
Naked crimping terminal: OT, 6 mm
2
,
M6, 50 A, tin plating, 12-8 AWG
Delivered with the
fittings
Signal cable to
the indoor and
outdoor units
(optional)
Electrical power cable, 300 V, SJTW, 3 x
16 AWG, black (three core wires), 10 A,
shielded outdoor cable, UL
The length is
determined by site
survey.
Naked crimping terminal, single-wire
cord end terminal, 1.5 mm
2
, 16 A, Red
Delivered with the
fittings
3.3 Space Requirements
3.3.1 Indoor Unit Space Requirements
Equipment Room Requirements
●
To ensure that the environment control system in the smart cooling product
room works properly, take moisture-proof and thermal insulation measures.
●
The equipment room should have good heat insulation, and the walls and
floor should be protected against moisture. The moisture-proof layer of the
ceiling and wall must be made of polyethylene film. The paint on the concrete
wall and floor must be moisture-proof.
●
Incoming outdoor air may increase the load of system heating, cooling,
humidification, and dehumidification. Therefore, it is recommended that
outdoor air be prevented from entering the equipment room. (The incoming