Figure 3-54 Removing the protective device for the lamp
----End
3.7.2 Connecting the signal cable to the HWA cable terminal
Prerequisites
NO TICE
Before connecting the NetCol8000-A100 signal cable between the high water level
detection switch and the HWA cable terminal, by referring to
Protective Device from the Infrared Humidifier Lamp
to remove the protective
device and the signal cable to the high water level detection switch from the
infrared humidifier lamp firstly.
Procedure
Step 1 Connect the signal cable to the HWA cable terminal routed over the high level
detection switch through cable holes. Then arrange cables and bind them on the
fix base of cable ties.
NO TE
Only NetCol8000-A100 needs to be connected onsite, NetCol8000-A050 has been
connected before delivery.
NetCol8000-A(050, 100) In-room Air Cooled Smart
Cooling Product
User Manual
3 Installation Guide