7.2 Alarm Reference
Table 7-8 Alarm reference
Alar
m ID
Alarm
Name
Alar
m
Sever
ity
Occurren
ce
Condition
s
Possible Causes
Solutions
a001 Return
-air
temp
invalid
Critic
al
The
temperatu
re exceeds
the
normal
range
during
normal
communic
ation, or
the sensor
on the
temperatu
re and
humidity
collection
board fails
to
communic
ate when
the alarm
detection
delay
expires.
1. Dirt or water exists
around the T/H
sensor, which leads
to a detection
fault.
2. The T/H sensor is
faulty.
1. Remove dirt
or water from
the T/H
sensor.
2. Maintain or
replace the
T/H sensor.
NetCol8000-A(050, 100) In-room Air Cooled Smart
Cooling Product
User Manual
7 System Operation and Maintenance
Issue 12 (2020-10-28)
Copyright © Huawei Technologies Co., Ltd.