Step 8
Choose
Maint
>
Performance Maint
on the home screen to access the
Performance Maint
screen. Then clear the humidifier runtime.
Step 9
Choose
Settings
>
System Settings
>
System Control
>
Humid
>
Action
.
----End
6.4.6 Replacing the Differential Pressure Switch
Prerequisites
The differential pressure switch needs to be replaced.
A spare differential pressure switch of the same model is available and functional.
Context
Tool: Phillips screwdriver
Procedure
Step 1
Tap
Shutdown
on the LCD home screen.
Exercise caution because the device is still energized after it is shut down on the LCD.
Step 2
Open the rear door, remove the air filter, and switch off general circuit breakers (AC1 and
AC2).
Step 3
Remove the pressure inlet tube from the differential pressure switch, use a Phillips
screwdriver to remove the four screws from the switch, and take out the switch.
Step 4
Remove the screws from the differential pressure switch cover, and remove the cable.
Figure 6-5
Removing a differential pressure switch