NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
6 System Operation and Maintenance
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
108
No. Operation
Troubleshooting
Period
Result
securely installed.
□Failed
20
Check that pipes do not
leak.
Close the water inlet
stop valve and repair
leaks.
Semi-annual
□Passed
□Failed
21
Check that the smart
cooling product
drainpipe is free from
leaks and blockages.
If the drainpipe
leaks, repair the
leaks. If the
drainpipe is blocked,
clear the blockage
inside the pipe.
Semi-annual
□Passed
□Failed
6.2 Alarm References
Table 6-2
Alarm list (V200R001 software version)
Alarm
ID
Alarm Name
Alarm
Severity
Impact
Possible Cause
Solution
a001
Return air 1/2
temperature
invalid
Major
Generates an
alarm
1. The cables to the
temperature sensor are
loose or damaged.
2. The temperature
sensor is faulty.
1. Check the cables to
the temperature
sensor.
2. Maintain or replace
the temperature
sensor.
Return air 2
temperature
invalid
Major
Generates an
alarm
1. The cables to the
temperature and
humidity sensor are
loose or damaged.
2. The temperature and
humidity sensor is
faulty.
1. Check the cables to
the temperature and
humidity sensor.
2. Maintain or replace
the temperature and
humidity sensor.
a002
Return air high
temperature
alarm
Critical
Generates an
alarm
1. The temperature
sensors or temperature
and humidity sensors
are located in
inappropriate positions.
2. The thermal load
power is high or the
cooling capacity is
insufficient.
3. The ambient
temperature exceeds
the upper threshold.
4. The high temperature
1. Adjust the positions
of the temperature
sensors or temperature
and humidity sensors.
2. Add smart cooling
products or contact
Huawei technical
support.
3. Measure the
ambient temperature.
Check whether other
causes exist if the
alarm persists in a