No.
Item
Note
6
Major alarms
indicates the number of active major
alarms.
7
Minor alarms
indicates the number of active minor
alarms.
8
Warnings
indicates the number of active
warnings.
9
Status bar
-
10
Alarm bar
You can tap
in the alarm
bar to enter the active alarm screen that
displays all active alarms.
11
Login button/Logout
button
indicates that you have not
logged in to the system, and can tap the icon
to log in.
indicates that you
have logged in to the system as admin or
operator user, and can tap the icon to log out.
12
Teamwork control
button
indicates that there is no teamwork
control at present.
indicates that there is
teamwork control without alarms at present.
indicates that there is teamwork control
with alarms at present.
6.5 Setting Parameters
6.5.1 Setting T/H Sensors Parameters
Prerequisites
●
The T/H sensors outside the cabinet need to be enabled when they are
installed, otherwise, skip
.
●
This section describes how to enable Cold aisle sensor 1.
Procedure
Step 1 On the home screen, choose Settings > System Settings > T/H sensor.
is displayed.
NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
6 Power-On Commissioning
Issue 08 (2021-09-17)
Copyright © Huawei Technologies Co., Ltd.
139