NetCol5000-A021 In-row Air Cooled Smart Cooling
Product
User Manual (208 V)
6 System Operation and Maintenance
Issue 03 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
211
Figure 6-25
Removing screws from a high liquid level detector
Step 5
Install the new liquid level detector and connect the interconnection terminal of the liquid
level detector.
Step 6
Tighten screws, connect cables, install the water pan cover, and close the front door.
----End
6.5.13 Replacing the Water Pump
Prerequisites
The water pump needs to be replaced.
A spare water pump of the same model is available and functional.
Tools: flat-head screwdriver, socket wrench.
Before removing the water pump, drain water from the water pan completely.
Context
The water pump can be maintained only from the front.
Procedure
Step 1
Tap
Shutdown
on the LCD home screen and turn off the smart cooling product switch in the
PDC.