NetCol5000-A021 In-row Air Cooled Smart Cooling
Product
User Manual (208 V)
6 System Operation and Maintenance
Issue 03 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
199
6.5.7 Replacing the Welded Filter Dryer with the Threaded Filter
Dryer
Prerequisites
The welded filter dryer needs to be replaced.
A spare threaded filter dryer of the same model is available and functional. The spare
threaded filter dryer consists of a filter dryer, entrance elbow (with a thread connector),
and exit straight tube (with a thread connector).
Tools: welding equipment, refrigerant retrieval device (configured based on local
conditions), Phillips screwdriver, nitrogen cylinder, refrigerant tank, vacuum pump,
pressure gauge, leather hose, protective gloves, two 27# adjustable wrenches, 36#
wrench
Preparation: Power off the indoor unit and reclaim all refrigerant from the system.
Context
shows the filter dryer before replacement.
replacement.
Procedure
Step 1
Tap
Shutdown
on the LCD home screen and turn off the smart cooling product switch in the
PDC and the compressor switch QF3.
Exercise caution because the NetCol5000-A is still energized when it is being shut down over
the LCD.
Step 2
Reclaim all refrigerant from the system using a refrigerant retrieval device to ensure that there
is no pressure inside the system.
Discharge the refrigerant if the local laws and regulations allow.
Step 3
Remove the liquid pipe NTC temperature sensor shown by (1) in
Step 4
Remove the welded filter dryer, as shown in