NetCol5000-A021 In-row Air Cooled Smart Cooling
Product
User Manual (208 V)
6 System Operation and Maintenance
Issue 03 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
188
Figure 6-5
Removing a fan assembly
Step 4
Install a new fan and fan guard, connect the connectors, and use a cable tie to secure the cable.
Step 5
Close the front door.
----End
Follow-up Procedure
Power on the NetCol5000-A, choose
Maint
>
Performance Maint
on the home screen, and
clear the indoor fan runtime.
6.5.3 Replacing the Differential Pressure Switch
Prerequisites
The differential pressure switch needs to be replaced.
A spare differential pressure switch of the same model is available and functional.
Tool: Phillips screwdriver
Context
The differential pressure switch can be maintained only from the rear.
Procedure
Step 1
Tap
Shutdown
on the LCD home screen and turn off the smart cooling product switch in the
PDC.