NetCol5000-A021 In-row Air Cooled Smart Cooling
Product
User Manual (208 V)
6 System Operation and Maintenance
Issue 03 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
147
Menu Item
Parameter
Record
Compressor
.
Discharge pressure
Suction pressure
Tap
Teamwork
.
Teamwork function
Choose
Teamwork
>
Teamwork
Settings
.
Total number of units
Number of active units
6.2.3 Monthly Maintenance
Table 6-3
Monthly maintenance checklist
Item
Method
Troubleshooting
Air filter
Check that the filter is not
blocked.
Clean the air filter (water cleaning is
recommended).
Check that the filter is not
damaged or distorted.
Replace the air filter.
Fan
Check that the indoor fan
guard is not distorted.
Maintain or replace the fan guard.
Check that the indoor fan
blades are intact.
Replace the fan.
Check that the indoor fan
does not generate abnormal
noise during operation.
Replace the fan.
Check that the screws on the
indoor fan are not loose or
distorted.
Tighten the screws.
Water pan
filter
Check that the condensate
pan and liquid level detector
have no dirt or scale.
Clean dirt or scale from the condensate
pan and liquid level detector.
Check that the water pan filter
is clean and not blocked.
Clean the water pan filter, by referring to
Compressor
Check that the compressor is
secured properly.
Tighten the compressor screws.
Check that there is no oil
stain on the compressor
service valve.
Clean the refrigerant oil on the valve.
Check that the sound of the
compressor is properly.
Replace the compressor.
Electrode
Check that the humidifier run
overtime alarm is not
Replace the electrode humidifier
Summary of Contents for NetCol5000-A021
Page 234: ......