NetCol5000-A 42 kW Air Cooled In-row Precision Air
Conditioner
User Manual
5 Operation and Maintenance
Issue 01 (2017-07-27)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
204
Figure 5-54
Installing a T/H sensor
Step 6
Install the air filter and close the rear door.
Step 7
Power on the device and tap
Startup
on the home screen. Ensure that the air conditioner is
running normally without any alarms.
----End
5.4.15 Replacing the LCD
Prerequisites
The LCD needs to be replaced.
A spare LCD with the correct software version is available. If the LCD software is
incorrect, upgrade the software by following the instructions in the
ACC Software
Upgrade Guide
.
Tool: Phillips screwdriver
Procedure
Step 1
Tap
Shutdown
on the ACC home screen.