NetCol5000-A 42 kW Air Cooled In-row Precision Air
Conditioner
User Manual
5 Operation and Maintenance
Issue 01 (2017-07-27)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
182
Figure 5-30
Installing a liquid level detector
Step 7
Install the water pan cover, and close the front door.
Step 8
Power on the device and tap
Startup
on the home screen. Ensure that the air conditioner is
running normally without any alarms.
----End
5.4.8 Replacing the Condensate Pump
Prerequisites
The condensate pump needs to be replaced.
A spare condensate pump of the same model is available and functional.
Tools: Phillips screwdriver, flat-head screwdriver, socket wrench
Before removing the condensate pump, drain water from the water pan completely.
Context
The condensate pump can be maintained only from the front door.