Figure 3-22 Leveling the cabinet
2. Use a measuring tape or right angle to check that the heights measured from
the front, rear, right, and left of the cabinet are the same.
----End
3.7 Installing an Outdoor Unit
For the details about how to install the outdoor unit, see the outdoor unit user
manual.
3.8 Exhausting Nitrogen
Context
D ANGER
Before welding refrigerant pipes, fully exhaust nitrogen from the refrigerant pipes
to avoid explosion and injuries.
Procedure
Step 1 Remove the valve bonnet of discharge pipe needle valve, as shown in
Connect the needle valves using rubber tubes with pressure gauge.
NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width)
3 Installation Guide
Issue 17 (2020-10-22)
Copyright © Huawei Technologies Co., Ltd.
50