NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (800 mm Width)
5 System Operation and Maintenance
Issue 05 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
113
Figure 5-14
Removing the module board
Step 6
Install a new module board and tighten the bolts. Bind cable ties and install cable terminals
according to the photo you have taken.
Step 7
Use a Phillips screwdriver to secure the rotate panel and reinstall the left front panel and top
cover.
Step 8
Power on the smart cooling product and ensure that it starts properly. Observe it for 30
minutes and ensure that no alarm is generated.
----End
5.4.2.4 Replacing a Safety Valve
Prerequisites
A safety valve needs to be replaced.
A spare safety valve of the same model is available and functional.
Context
Tools: Phillips screwdriver, torque wrench, 557 glue, refrigerant retrieval device
(required based on local conditions), nitrogen injection and pressure preservation tool,
vacuumization tool, and refrigerant injection tool.
Preparation: Power off the outdoor unit and empty the system of refrigerant.