Procedure
Step 1 Press MENU on the PDU2000 display panel.
Step 2 Press UP until
is displayed and ADD blinks.
Step 3 Press MENU,
is displayed, and 01 blinks. The current device address is 01.
Step 4 Press UP or DOWN to select the device address value.
Step 5 Press MENU to confirm the setting.
●
If
is displayed, the setting succeeds.
●
If
is displayed, the setting fails. Reset the parameter.
NO TE
The PDU2000 BaudRate, DataBit, StopBit, and Parity cannot be set on the WebUI. Their
values are 9600, 8, 1, and None respectively.
Step 6 Press Button. is displayed. Then press MENU to exit.
Step 7 Set RS485 port parameters for the collector based on the value of BaudRate,
DataBit, StopBit, and Parity of the device. For ECC800-Pro collector settings, see
6.5.1.4 Setting RS485 Parameters for the ECC800-Pro Collector
----End
6.5.9.2 Creating an rPDU on the NetEco
This section describes how to create an rPDU on the NetEco.
Prerequisites
●
You have the operation rights for Planning Configuration.
●
You have created a management domain for the device to be added on the
Planning Configuration page.
●
The ECC800-Pro connected to the device has been connected to the NetEco.
●
Transparent transmission has been enabled for the COM port on the ECC800-
Pro or UIM20A expansion module to which the device is connected.
Procedure
Step 1 Log in to the NetEco client.
Step 2 On the main menu, choose Device Management > Configuration > Planning
Configuration.
Step 3 Choose the management domain where you want to create a device from the
navigation tree on the left.
iMaster NetEco
Device Installation and Commissioning Guide (Data
Center)
6 Adding Devices
Issue 02 (2021-05-12)
Copyright © Huawei Technologies Co., Ltd.