IDS1000-A Air-Cooled Container Data Center
All-in-One Maintenance Guide
5 Parts Replacement
Issue 01 (2016-01-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
121
Figure 5-38
Setting the access controller IP address
Use a small-sized flat-head screwdriver to operate the DIP switch on the access controller to set the
access controller IP address.
Step 4
Install the new access controller and reconnect the terminal blocks and network cable.
Install terminals on the left and right of the access controller based on the mapping between cable labels
and the silk screens on the access controller.
Step 5
Secure the access controller.
Step 6
Switch on the circuit breaker for the access controller, and check whether the access controller
is working properly.
The access controller is working properly if the container door can be opened from outside using an
access card and from inside using the exit button, and the door opening operation is logged in the
monitoring system.
----End
Follow-up Procedure
Dispose of the removed access controller that is confirmed faulty.
5.4 Replacing Fire Extinguishing System Components
(Standard)
5.4.1 Replacing a Smoke Detector
Prerequisites
A smoke detector needs to be replaced.
A spare smoke detector of the same model is available and functional.