4.1 Installation Environment Requirements
NOTE
For details about the safety precautions to be observed when you install or replace servers and their parts, see
.
Space
l
Install the G5500 in an access-restricted area.
l
Keep the area where the server is located clean and tidy.
l
Maintain a clearance of 800 mm (31.50 in.) at the front and rear of the cabinet to
facilitate heat dissipation and device maintenance.
The server draws in cool air from the front and exhausts hot air from the rear. Therefore,
the front and rear of the cabinet must be well-ventilated for optimal heat dissipation.
Cabinet
l
Use a standard 19-inch cabinet that is more than 1000 mm (39.37 in.) deep and complies
with the International Electrotechnical Commission 297 (IEC 297) standard.
A G5500 is 4U high and stackable. No spacing needs to be reserved in between.
l
Install air filters on cabinet doors.
l
Provide AC power supply from the rear of the cabinet.
Temperature and Humidity
l
Use temperature control devices all year long in any climate.
l
In dry and humid areas, maintain ambient humidity within range with humidifiers and
dehumidifiers respectively.
Table 4-1
Equipment Room
Item
Specifications
Temperature
5°C to 40°C (41°F to 104°F)
Humidity
8% RH to 90% RH (non-condensing)
4.2 Installing the Chassis
Procedure
Step 1
Determine the positions for installing the guide rails.
Before installing guide rails, determine the positions for installing guide rails according to the
configuration scheme.