FusionModule800 Smart Small Data Center
Maintenance Guide
5 Parts Replacement
Issue 02 (2016-11-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
55
When removing cables, remove the battery cable below the battery MCB first.
After removing cables, insulate the cable terminals.
When removing cables, label the cables with corresponding terminal ports for later
connection.
Figure 5-22
Removing a battery MCB
Step 5
Push the buckle at the battery MCB outwards using a flat-head screwdriver, and remove the
faulty battery MCB.
Step 6
Install the new battery MCB by referring to the preceding method, connect cables, and tighten
screws.
Step 7
Reinstall the removed components, and close the corresponding cabinet door.
----End
5.2.15 Replacing a Battery Current Sensor