4 Preparations for Power-On Commissioning
Issue 02 (2017-01-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
16
----End
4.5.4 Verifying the Setting of the Automatic Water Refill Valve
Prerequisites
The water pressure of the auxiliary water refill device meets the requirement.
Preparations
Tool: adjustable wrench
Documents: pipe system diagram, pipe system valve control relationship table
Skill requirement: cooling engineer
For the diagrams and tables, see the initial configuration parameter manual for the solution in use.
Context
The setting of the automatic water refill valve is critical for the stable running of the cooling
system.
The automatic water refill valve has been factory set to 0.15 MPa. In case of accidental
changes during the transportation or installation, verify the valve setting before starting the
system.
Procedure
Step 1
Close the service valve for the automatic water refill valve.