FusionModule1000A40 IT Solution
Maintenance Guide (2016.05, AI Version)
3 Maintenance
Issue 04 (2018-01-05)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
16
Device
Operation
Check
Standard
Troubleshooting
All devices of
the fire
extinguisher
are free from
rust on the
exterior, and
the coating is
intact.
Repaint.
The lead seal
and safety
signs on
hand-operated
devices of the
fire cylinder
are intact.
Replace the electric control head.
Check the pressure
pointer of the fire
cylinder.
The pressure
pointer is in
the green zone.
Ask a fire engineer to check
whether the fire cylinder leaks
extinguishant. If leakage occurs, the
fire engineer charges the
extinguishant in the local charging
station.
Emergency
light
Disconnect the
power plug of the
emergency light.
The
emergency
light turns on.
Replace the emergency light.
3.2.6 Fire Extinguishing System (CE Tyco)
Table 3-7
Monthly maintenance checklist for the fire extinguishing system
Device
Operation
Check Standard
Maintenance Guide
Extinguisha
nt control
panel
Check indicators
on the
extinguishant
control panel.
The power indicator
turns on, and the
alarm indicator turns
off.
Replace the extinguishant
control panel.
Extinguisha
nt control
panel
batteries
Check the battery
terminals.
The wiring terminals
are in good
condition without
corrosion.
Clean the contaminated and
corroded terminals. Replace
the batteries with severely
corroded terminals for the fire
alarm control panel.
Fire
extinguisher
Check the
appearance of the
fire cylinder,
electrical actuator,
pneumatic switch,
All devices of the
fire extinguisher are
intact, free from
deformation and
mechanical damage.
Replace the fire cylinder. For
details about how to replace
other devices, contact Huawei
technical support.