FusionModule1000A40 IT Solution
Maintenance Guide (2016.05, AI Version)
3 Maintenance
Issue 04 (2018-01-05)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
9
Cate
gory
Item
Method
Expected
Result
Troubleshooting
The coverage of
the camera is
optimal.
If the area covered by the
camera is inappropriate,
adjust the camera coverage
by following the instructions
in documents delivered with
the camera.
Access
controller
communic
ation
status
Check the door
status list in the
management
system.
All door status
icons under the
access controller
blink.
If a door status icon is
dimmed (unavailable), check
the access controller and
network status.
3.2 Monthly Maintenance
3.2.1 Power Supply and Distribution System
Table 3-2
Monthly maintenance checklist for the power supply and distribution system
Item
Method
Expected
Result
Troubleshooting
Luminance
of the
three-phase
indicators
Check the
luminance of the
three-phase
indicators.
The
three-phase
power
indicators are
steady on.
Replace an indicator if it generates
no or dim light.
SPD
indicator
and SPD
circuit
breaker
status
Check the SPD
indicator and SPD
circuit breaker
status.
The SPD
indicator is
green.
If an SPD indicator is red, replace
the SPD in a PDC..
The SPD
circuit breaker
is switched on.
If an SPD circuit breaker is
switched to OFF, switch it to ON.
Buttons on
the PD510
electricity
meter panel
Push any button on
the PD510
electricity meter
panel.
The PD510
electricity
meter LCD
lights up and
displays
information
properly.
1.
If the LCD does not display
information properly (no display
or fuzzy), check whether the
power cable is properly
connected.
2.
If the power cable is correctly
connected, Replace the PD510
electricity meter.