Table 4-5 Cable terminal requirements
Port
Connection
Method
Bolt
Specificatio
ns
Torque
Remarks
Active input
Crimped DT
terminals
M10
20 N·m
Standard
configuratio
n, delivered
with the
product.
Standby
input
Crimped DT
terminals
M10
20 N·m
Standard
configuratio
n, delivered
with the
product.
4.3 Installing a FusionCol8000-E
4.3.1 Unpacking and Checking
Procedure
Step 1 Verify that the package is intact. If any damage is found, notify the carrier
immediately.
Step 2 Remove the plastic packaging materials.
Step 3 Check the types and quantity of fittings according to the fitting list. If any fitting is
missing, contact Huawei technical support.
----End
FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
4 System Installation (FDC Scenario)
Issue 02 (2021-04-15)