●
Cables should be securely connected and free of contact with components,
such as the fan.
●
When laying out cables, ensure that the power cables and signal cables are
reliably separated and that electric and extra low voltage (ELV) cables are
bound separately.
●
Cable colors in this document are for reference only.
3.4.2 Cable Routes
Figure 3-19 Cable routes
(1) Power cable
(2) Exhaust air damper cable
(3) Supply air damper cable
(4) Electric heater controller
cable
(5) Signal cable
3.4.3 (Optional) Installing Signal Cables
Prerequisites
Signal cables must be routed through protective tubes for protection.
The device can be connected to a smoke sensor, remote startup/shutdown signal,
public alarm signal, and water sensor. The following describes how to connect a
water sensor.
Context
Figure 3-20 Signal cable terminal (using X501 as an example)
FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
3 System Installation (Building Scenario)
Issue 02 (2021-04-15)
Copyright © Huawei Technologies Co., Ltd.
49