Parameter
Description
Link mode
● Server: The smart cooling product works as the
server and can connect to two clients for
communication.
● Client: The smart cooling product works as the
client and can connect to a remote server for
communication.
● Server and client: The smart cooling product works
as the server and can connect to two clients for
communication. It also works as the client and can
connect to a remote server for communication.
Client encryption
This parameter is configurable when Link mode
involves Client.
Server encryption
This parameter is configurable when Link mode
involves Server.
Encryption algorithm
CBC
Specifies whether to use the CBC encryption algorithm.
After the parameter setting is changed, the system
automatically restarts. Exercise caution with the setting.
NMS IP address
Enter the actual IP address of the NMS. The IP
addresses of the display board, client NMS, and server
NMS must be unique.
This parameter is configurable when Link mode
involves Client.
NMS port number
This parameter is configurable when Link mode
involves Client.
● Connecting to the NetEco: Set this parameter to
32907 if Client encryption is enabled, or set it to
32906 if Client encryption is disabled.
● Connecting to other NMSs: You are advised not to
change the value. In special cases, set this
parameter based on the site requirements.
Pre-shared password
Secondary authentication password used for Modbus-
TCP connection.
----End
7.4.4.3 Setting Communications Parameters (SNMP Protocol)
Context
●
To set communications parameters, log in as the admin user.
●
This section is suitable only for SNMP. Skip this section if you use Modbus.
●
Record the values entered in this section. They will be used when you connect
a unit to a network management system (NMS).
FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
7 Power-On Commissioning
Issue 03 (2021-04-20) Copyright © Huawei Digital Power Technologies Co., Ltd.
125