Attribute
Alarm ID
Alarm Severity
Alarm Type
65542
Critical
Fault alarm
Parameter
Parameter
Description
Frame
Subrack number of the EDFA
Slot
Slot number of the EDFA
PUMP
PUMP ID. Value: 2
current pump
temperature
Actual temperature of EDFA PUMP2
Impact on the System
The EDFA service life is affected.
Possible Cause
The temperature of PUMP2 exceeds the upper threshold.
The temperature of PUMP2 is below the lower threshold.
Handling Procedure
Check whether the temperature alarm threshold is set to a proper value. If it is set to a proper
value, contact Huawei.
Alarm Clearing Condition
When the temperature of PUMP2 is between the upper and lower thresholds, the alarm is
cleared.
2.3.4 Fan Alarms
2.3.4.1 ALM-4097 Fan Speed Alarm
Description
When the fan-rotating speed is lower than 800 rpm, this alarm is generated.
EDFA0820-D
Routine Maintenance Guide
2 Common Alarm Handling
Issue 02 (2018-07-02)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
17