ACBox 12-In 1-Out AC Combiner Box
User Manual
4 Installation
Issue 03 (2018-05-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
13
Type
Tools and Instruments
PPE
Safety goggles
Anti-dust respirator
Safety gloves
Safety shoes
N/A
N/A
4.3 Determining the Installation Position
Basic Requirements
The ACBox is protected to IP65 and can be installed indoors or outdoors.
Do not install the ACBox in areas with flammable or explosive materials.
Installation Environment Requirements
The ACBox must be installed in a well-ventilated environment to ensure good heat dissipation,
so that the ACBox can operate in the temperature range of –20°C to +50°C.
Mounting Structure Requirements
The mounting structure where the ACBox is installed must be fireproof.
Do not install the ACBox on flammable building materials.
The ACBox weighs 46 kg. Ensure that the installation surface is solid enough to bear the
weight load.
Installation Space Requirements
The ACBox enclosure dimensions (W x H x D) are 780 mm x 815 mm x 225 mm. The
ACBox can be mounted on a wall, pole, or support. Reserve sufficient space around the
ACBox to facilitate installation and cable connection.