HTW HTW-MI100Q4DHN1D Installation Manual Download Page 17

16 

installation manual 

8.3 Main board Code designation

8.3 Main board Code designation

● 

1 means factory test mode

● 

0 means add. auto searching mode

      (default setting)

● 

1 means DC fan Is chosen 

● 

0 means AC fan Is chosen

 

00 means DC fan static pressure is 0

      (reserved)

● 

01 means DC fan static pressure is 1

      (reserved)

 

10 means DC fan static pressure is 2

      (reserved)

 

11 means DC fan static pressure is 3

       (reserved)

1 2 3 4 

S W 1 

O N 

1 2 3 4 

S W 1 

O N 

1 2 3 4 

S W 1 

O N 

1 2 3 4 

S W 1 

O N 

1 2 3 4 

S W 1 

O N 

1 2 3 4 

S W 1 

O N 

SW1 

definition 

● 

00 means the temperature is 15

        degrees when shutting down the unit
        for cold wind proof.

● 

01 means the temperature is 20 

        degrees when shutting down the
        unit for cold wind proof.

● 

10 means the temperature is 24 

        degrees when shutting down the 
        unit for cold wind proof.

● 

11 means the temperature is 26

        degrees when shutting down the 
        unit for cold wind proof.

● 

00 means the time of stopping 

        TERMAL fan is 4 minutes

● 

01 means the time of stopping 

        TERMAL fan is 8 minutes  

● 

10 means the time of stopping 

        TERMAL fan is 12 minutes 

● 

11 means the time of stopping 

        TERMAL fan is 16 minutes  

1 2 3 4 

S W 2 

O N 

1 2 3 4 

S W 2 

O N 

1 2 3 4 

S W 2 

O N 

1 2 3 4 

S W 2 

O N 

1 2 3 4 

S W 2 

O N 

1 2 3 4 

S W 2 

O N 

1 2 3 4 

S W 2 

O N 

1 2 3 4 

S W 2 

O N 

SW2 

definition 

 00 means temperature compensation is 

     6 degrees under heating mode

 

10 means temperature compensation

       is 4 degrees under heating mode

 

11 means temperature compensation

       is 8 degrees under heating mode

 

01 means temperature compensation is 

      2 degrees under heating mode

1   2  

S W 5 

O N 

1   2  

S W 5 

O N 

1   2  

S W 5 

O N 

1   2  

S W 5 

O N 

SW5 

definition 

 

1 means old display panel

 

0 means new display panel

 

1 means auto wind under auto mode

 

0 means auto wind under non auto mode

reserved

1   2  3 

S W 6 

O N 

1   2  3 

S W 6 

O N 

1   2  3 

S W 6 

O N 

SW6 

definition 

J1 no Jumpers means power
 off memory function

J1 Jumpers means no power 
off memory function

reserved

J1,J2 

definition 

J1 

J1 

J2 

Summary of Contents for HTW-MI100Q4DHN1D

Page 1: ...NGLISH 4 way CASSETTE type 90x90 HTW MI45Q4DHN1D HTW MI56Q4DHN1D HTW MI71Q4DHN1D HTW MI80Q4DHN1D HTW MI100Q4DHN1D HTW MI140Q4DHN1D Thanks for choossing our product Please read carefully this manual be...

Page 2: ...ust be properly arranged so that control board cover is fixed properly If control board cover is not fixed perfectly it will cause heat up at connection point of terminal fire or electrical shock If t...

Page 3: ...er Do not connect the ground wire to gas or water pipes lightning rod or a telephone ground wire Incomplete grounding may result in electric shocks Be sure to install an earth leakage breaker Failure...

Page 4: ...k 6 Connective pipe for restriction assembly 7 Soundproof insulation sheath 8 Out let pipe sheath 9 Out let pipe clasp 10 Tightening band 16 Remote contronller owner s manual 17 Installation manual 13...

Page 5: ...oil permeates G Place where strong electromagnetic waves exist H Place where flammable gases or materials exist I Place where acid or alkali gases evaporate J Other special environments 1000mm 1000mm...

Page 6: ...d cables To balance the ceiling and to avoid vibration please enforce the ceiling when necessary Adjust the hexangular nuts on the four installation hooks evenly to ensure the balance of the body Sele...

Page 7: ...iling Main body Hexagon nut For adjust to balance Drain pipe Electrical restricting assembly Main body of the unit Ceiling Indoor unit model 8000W 9000W NOTE All the pictures in this manual are for ex...

Page 8: ...ial is the high quality carbon steel galvanized or covered other rust preventive materials on the surface or rustless steel The ceiling rust prevention measure is conducted according to actual constru...

Page 9: ...ay motor Hook bolt Sway motor Drain pipe joint Water receiver hook Panel hook Piping joint panel sponge body Ceiling panel panel foam1 air out Fan panel foam 2 4 6 m m outlet foam Fig 4 16 Fig 4 15 1...

Page 10: ...on duct In case of one duct connection The air volume in duct is around 300 360m3 h for 5600W to 8000W unit The air volume in duct is around 400 640m3 h for 9000W to 15500W unit The max length of duct...

Page 11: ...backflow into unit inside during shutdown the drain pipe shall place down side and drain water to outdoor drain side the gradient of the drain pipe should be higher than 1 100 without salient and wate...

Page 12: ...n malfunction occur During normal operation please ensure that this plug is stuffed tightly to prevent water leakage 6 INSTALL THE CONNECING PIPE 6 1 The connective length of indoor and outdoor piping...

Page 13: ...onnection wires Use wrapping tape to tie them tight Do not let air penetrate into it lest condensation and drips of moist 3 Pull the connective wrapped connective pipe from outdoor through the sheath...

Page 14: ...d with external grounding wire reliable 2 Electric wiring must be done by professionals and wiring according to the wiring label 3 Fixing circuit must be wired with an a11 poledisconnection device at...

Page 15: ...wire Please apply the attached thermal insulation material to seal the jointing part of the pipe Failure sealing would lead to condensation 7 6 Wires in panel Wire the wires holder of swinging motor...

Page 16: ...nit there is no need to control indoor unit separately for details please refer to V4 outdoor unit manual 3 For previous control of indoor units the network can be set by connecting X Y E terminals th...

Page 17: ...wn the unit for cold wind proof 00 means the time of stopping TERMAL fan is 4 minutes 01 means the time of stopping TERMAL fan is 8 minutes 10 means the time of stopping TERMAL fan is 12 minutes 11 me...

Page 18: ...stop valves are both opened The air conditioner is pre heated by turning on the power Set the air conditioner under the mode of COOLING with the remote controller and check the following points If th...

Page 19: ...C Industria 13 l Pol gono Industrial El Pedregar 08160 Montmel Barcelona Spain Phone 0034 93 390 42 20 Fax 0034 93 390 42 05 info htwspain com www htwspain com...