HTW HTW-MI100Q4DHN1D Installation Manual Download Page 14

13 

installation manual 

CAUTION 

Please beware when install connective pipe, do not let any air, 
dust or other foreign substance invading into system. 
Pipes connection could be conducted after the indoor and 
outdoor unit are be fixed. 
Connective pipe must keep in dry when installation, do not let 
water invade in it.  
Connective copper pipe must be wrapped insulation layer (at 
least 9 mm thickness). 
The temperature of refrigerant circuit will be high, please keep 
the interconnection cable away from the copper tube 
 

6.5 Air expels 

Apply vacuum pump expels air from refrigerant charging vent of 
air side in outdoor unit. 
It is forbidden to apply the refrigerant inside of indoor unit for 
vacuum air. 

6.6 Open valve 

Employ a 5 mm hexagon spanner to open the valve spool of 
indoor and outdoor unit.  

6.7 Leak detection 

Use soap water to check whether gas leakage exists at the 
adapters 

6.8 Thermal insulation 

To process the thermal insulation for air side and liquid side 
piping. Please insulted the air side and liquid side piping 
completely, in the reason of during operate cooling mode the 
ambient temperature is very low. 

1) Thermal insulation at least 120 C material shall be apply for air 
side piping. 
2) Apply attached thermal insulation material to wrap the 
connective part of indoor piping tightly without gap. 

Fig.6-6 

Unit body 

Subsidiary belt of thermal  
insulation pump  

Field piping side 

Cut it from up to down 

7.    WIRING 

CAUTION 

1) Special power shall be applied within rated voltage range. 
External circuit of this air conditioner must be grounded that 
means power cable of outdoor unit shall be jointed with external 
grounding wire reliable.   
 
2) Electric wiring must be done by professionals, and wiring 
according to the wiring label. 
 
3) Fixing circuit must be wired with an a11-poledisconnection 
device at least 3mm switching distance of contact. 
 
4) Setting the electrical leakage device according to national 
regulation. 
 
5) Power cables and signal wires shall be arranged orderly and 
be wired rational without mutual interfere, and connective pipes 
and body of valves without mutual contact among them.   
 
6) The attached connective wire is 10m, provided that the 
length were not long enough, you must replace it by an 
appropriate length connective wire in the same specification. In 
a normal circumstance, it is not allowed to overlapping the two 
wires, but welded fix and wrapped by insulation adhesive band 
is except.  
 
7) an all-pole disconnection device which has at least 3mm 
separation distance in all pole and a residual current 
device(RCD)with the rating of above 10mA shall be incorpo-
rated in the fixed wiring according to the national rule. 
 
8) All electric wiring is finished, you could input power as long 
as confirm that all wires connect are correct and fix tightly. 
 

7.1 Electrical wiring 

Item 

Model:MDV-D 

2800W~15500W

Power supply of indoor part 

Power supply: 

Power supply: 

Signal-phase 

220

-

240V

~, 

50Hz  

Signal-phase 

208

-

230V~,  

60Hz 

Power switch 

Capacity 

Safety  
 fuse 

15A 

15A 

Power cable 

Below 20m  Below 50m 

2X4.0mm

2X4.0mm

2X2.5mm

2X2.5mm

Connect wiring 

Signal wire of indoor  
  and outdoor unit 

Wire diameter 

Ground Line 

Signal line 

2.0mm

Shielded wire 

  3X0.75mm

7.2 Power specification 

The power cable specifications are as follows. In case power capacity is too low may result in over-heating of piping that would be  
burned out the unit.  

15A 

15A 

Signal line 

2.0mm

Shielded wire 

  3X0.75mm

Table 7-1 

Summary of Contents for HTW-MI100Q4DHN1D

Page 1: ...NGLISH 4 way CASSETTE type 90x90 HTW MI45Q4DHN1D HTW MI56Q4DHN1D HTW MI71Q4DHN1D HTW MI80Q4DHN1D HTW MI100Q4DHN1D HTW MI140Q4DHN1D Thanks for choossing our product Please read carefully this manual be...

Page 2: ...ust be properly arranged so that control board cover is fixed properly If control board cover is not fixed perfectly it will cause heat up at connection point of terminal fire or electrical shock If t...

Page 3: ...er Do not connect the ground wire to gas or water pipes lightning rod or a telephone ground wire Incomplete grounding may result in electric shocks Be sure to install an earth leakage breaker Failure...

Page 4: ...k 6 Connective pipe for restriction assembly 7 Soundproof insulation sheath 8 Out let pipe sheath 9 Out let pipe clasp 10 Tightening band 16 Remote contronller owner s manual 17 Installation manual 13...

Page 5: ...oil permeates G Place where strong electromagnetic waves exist H Place where flammable gases or materials exist I Place where acid or alkali gases evaporate J Other special environments 1000mm 1000mm...

Page 6: ...d cables To balance the ceiling and to avoid vibration please enforce the ceiling when necessary Adjust the hexangular nuts on the four installation hooks evenly to ensure the balance of the body Sele...

Page 7: ...iling Main body Hexagon nut For adjust to balance Drain pipe Electrical restricting assembly Main body of the unit Ceiling Indoor unit model 8000W 9000W NOTE All the pictures in this manual are for ex...

Page 8: ...ial is the high quality carbon steel galvanized or covered other rust preventive materials on the surface or rustless steel The ceiling rust prevention measure is conducted according to actual constru...

Page 9: ...ay motor Hook bolt Sway motor Drain pipe joint Water receiver hook Panel hook Piping joint panel sponge body Ceiling panel panel foam1 air out Fan panel foam 2 4 6 m m outlet foam Fig 4 16 Fig 4 15 1...

Page 10: ...on duct In case of one duct connection The air volume in duct is around 300 360m3 h for 5600W to 8000W unit The air volume in duct is around 400 640m3 h for 9000W to 15500W unit The max length of duct...

Page 11: ...backflow into unit inside during shutdown the drain pipe shall place down side and drain water to outdoor drain side the gradient of the drain pipe should be higher than 1 100 without salient and wate...

Page 12: ...n malfunction occur During normal operation please ensure that this plug is stuffed tightly to prevent water leakage 6 INSTALL THE CONNECING PIPE 6 1 The connective length of indoor and outdoor piping...

Page 13: ...onnection wires Use wrapping tape to tie them tight Do not let air penetrate into it lest condensation and drips of moist 3 Pull the connective wrapped connective pipe from outdoor through the sheath...

Page 14: ...d with external grounding wire reliable 2 Electric wiring must be done by professionals and wiring according to the wiring label 3 Fixing circuit must be wired with an a11 poledisconnection device at...

Page 15: ...wire Please apply the attached thermal insulation material to seal the jointing part of the pipe Failure sealing would lead to condensation 7 6 Wires in panel Wire the wires holder of swinging motor...

Page 16: ...nit there is no need to control indoor unit separately for details please refer to V4 outdoor unit manual 3 For previous control of indoor units the network can be set by connecting X Y E terminals th...

Page 17: ...wn the unit for cold wind proof 00 means the time of stopping TERMAL fan is 4 minutes 01 means the time of stopping TERMAL fan is 8 minutes 10 means the time of stopping TERMAL fan is 12 minutes 11 me...

Page 18: ...stop valves are both opened The air conditioner is pre heated by turning on the power Set the air conditioner under the mode of COOLING with the remote controller and check the following points If th...

Page 19: ...C Industria 13 l Pol gono Industrial El Pedregar 08160 Montmel Barcelona Spain Phone 0034 93 390 42 20 Fax 0034 93 390 42 05 info htwspain com www htwspain com...

Reviews: