5.  LAYOUT THE DRAIN PIPE 

5.1 Install the drain pipe of indoor unit 

 
1) The drainpipe can use PVC pipe (external diameter about 37

39mm, inner diameter is 32mm).  
 
2) Joint drainpipe connector to the end side of water pumping pipe, 
and fix drainpipe together with water outflow pipe and thermal 
insulation tube by clasp of water outflow pipe (attached).   

CAUTION 

Don’t use forcing strength to crack the water-pumping pipe.  

CAUTION 

The joints in drain system must be sealed to avoid water leakage. 

9) The height from floor to the end of drainpipe or the bottom of 
drain slot must more than 50 mm. Don’t immerse the end of 
drainpipe or the bottom of drain slot into water. When drain 
condensate liquid to raceway, please bend the drainpipe to a 
U-sharped hydroseal for avoiding stench transmitted by drainpipe 
to indoor.        

0.8~1.0 m

a   

>1.0 m 

 Fig.5-1 

Gradient:  
higher than 1/100 

CAUTION 

3) Water-pumping pipe and drainpipe from main body must be 
wrapped by insulation tube evenly, and bound by tighten band for 
obstructing air getting in and coagulation. 
 
4) Prevent from water backflow into unit inside during shutdown, 
the drain pipe shall place down side and drain water to outdoor 
(drain side), the gradient of the drain pipe should be higher than 
(1/100), without salient and water remain.(

Refer to

 

Fig.5-1 a

 
5) When connecting drainpipe, don’t drag the pipe that would pull 
the main unit. For this, please arrange bearing points every 0.8 to 
1.0 meter to avoid pipe be bended (See 

Fig.5-1 b

). 

 
6) When connect a lengthen drainpipe, apply protective tube to 
wrap its indoor parts for ensuring the lengthen part connected 
tightly.    
 
7) In case the drainpipe outlet is higher than pumping connective 
pipe of the main body, the drainpipe must be arranged upwards 
vertically by using connective assembly of the water outlet for 
vertical bending, and the height of the drainpipe shall set to the 
defrosting pan surface no more than 1000mm, otherwise, too much 
backflow while shutdown would leads to overflow (

Refer to

 

Fig.5-2

). 

 
8) Base on the actual requirement to bend piping, and use 
connective assembly of water outlet in terminal box for pipe layout. 

50~100mm 

50~100mm 

50~100mm 

Max. 1000mm 

200mm 

200mm 

200mm 

Drainpipes from many units confluent water to main drainpipe and discharge to cloacae.  

Fig. 5-2 

Connective assembly of water outlet 

Main drainpipe 

Gradient: 1/50~1/100  

Summary of Contents for HTW-MI100Q4DHN1D

Page 1: ...NGLISH 4 way CASSETTE type 90x90 HTW MI45Q4DHN1D HTW MI56Q4DHN1D HTW MI71Q4DHN1D HTW MI80Q4DHN1D HTW MI100Q4DHN1D HTW MI140Q4DHN1D Thanks for choossing our product Please read carefully this manual be...

Page 2: ...ust be properly arranged so that control board cover is fixed properly If control board cover is not fixed perfectly it will cause heat up at connection point of terminal fire or electrical shock If t...

Page 3: ...er Do not connect the ground wire to gas or water pipes lightning rod or a telephone ground wire Incomplete grounding may result in electric shocks Be sure to install an earth leakage breaker Failure...

Page 4: ...k 6 Connective pipe for restriction assembly 7 Soundproof insulation sheath 8 Out let pipe sheath 9 Out let pipe clasp 10 Tightening band 16 Remote contronller owner s manual 17 Installation manual 13...

Page 5: ...oil permeates G Place where strong electromagnetic waves exist H Place where flammable gases or materials exist I Place where acid or alkali gases evaporate J Other special environments 1000mm 1000mm...

Page 6: ...d cables To balance the ceiling and to avoid vibration please enforce the ceiling when necessary Adjust the hexangular nuts on the four installation hooks evenly to ensure the balance of the body Sele...

Page 7: ...iling Main body Hexagon nut For adjust to balance Drain pipe Electrical restricting assembly Main body of the unit Ceiling Indoor unit model 8000W 9000W NOTE All the pictures in this manual are for ex...

Page 8: ...ial is the high quality carbon steel galvanized or covered other rust preventive materials on the surface or rustless steel The ceiling rust prevention measure is conducted according to actual constru...

Page 9: ...ay motor Hook bolt Sway motor Drain pipe joint Water receiver hook Panel hook Piping joint panel sponge body Ceiling panel panel foam1 air out Fan panel foam 2 4 6 m m outlet foam Fig 4 16 Fig 4 15 1...

Page 10: ...on duct In case of one duct connection The air volume in duct is around 300 360m3 h for 5600W to 8000W unit The air volume in duct is around 400 640m3 h for 9000W to 15500W unit The max length of duct...

Page 11: ...backflow into unit inside during shutdown the drain pipe shall place down side and drain water to outdoor drain side the gradient of the drain pipe should be higher than 1 100 without salient and wate...

Page 12: ...n malfunction occur During normal operation please ensure that this plug is stuffed tightly to prevent water leakage 6 INSTALL THE CONNECING PIPE 6 1 The connective length of indoor and outdoor piping...

Page 13: ...onnection wires Use wrapping tape to tie them tight Do not let air penetrate into it lest condensation and drips of moist 3 Pull the connective wrapped connective pipe from outdoor through the sheath...

Page 14: ...d with external grounding wire reliable 2 Electric wiring must be done by professionals and wiring according to the wiring label 3 Fixing circuit must be wired with an a11 poledisconnection device at...

Page 15: ...wire Please apply the attached thermal insulation material to seal the jointing part of the pipe Failure sealing would lead to condensation 7 6 Wires in panel Wire the wires holder of swinging motor...

Page 16: ...nit there is no need to control indoor unit separately for details please refer to V4 outdoor unit manual 3 For previous control of indoor units the network can be set by connecting X Y E terminals th...

Page 17: ...wn the unit for cold wind proof 00 means the time of stopping TERMAL fan is 4 minutes 01 means the time of stopping TERMAL fan is 8 minutes 10 means the time of stopping TERMAL fan is 12 minutes 11 me...

Page 18: ...stop valves are both opened The air conditioner is pre heated by turning on the power Set the air conditioner under the mode of COOLING with the remote controller and check the following points If th...

Page 19: ...C Industria 13 l Pol gono Industrial El Pedregar 08160 Montmel Barcelona Spain Phone 0034 93 390 42 20 Fax 0034 93 390 42 05 info htwspain com www htwspain com...

Reviews: