HTW HTW-MI100Q4DHN1D Installation Manual Download Page 10

installation manual 

 Fig.4-20 

Slide the four sliders in 
the corresponding 
channel when installing 
the cover. 

Installation cover’s rope 

Tap screw 

Slug 

 Fig.4-20 

 Fig.4-21 

 Fig.4-22 

 Fig.4-23 

 Fig.4-24 

Fresh air

Distribution duct

Distribution duct

Distribution duct

Distribution duct

The side with dectrical 
throttle couldn’t be connected 
with distribution duct.

4.6   Install the distribution duct 

Conditioned air can be distributes by means of a distribution duct. 

  In case of one duct connection 

    The air volume in duct is around 300-360m3/h for 5600W to 8000W unit 
    The air volume in duct is around 400-640m3/h for 9000W to 15500W unit 
    The max. length of duct is 2m 
    The original air outlet with the same direction of duct should be sealed 

  In case of two duct connection 

    The air volume in one duct is around 200-260m3/h for 5600W to 8000W unit 
    The air volume in one duct is around 300-500m3/h for 9000W to 15500W unit 
    The max. length of duct is 1.5m for one duct 
    The original air outlet with the same direction of duct should be sealed 

5600-8000W                     Series A=350mm; Series  B=85mm
9000-15500W                   Series A=350mm; Series  B=155mm

NOTE 

Summary of Contents for HTW-MI100Q4DHN1D

Page 1: ...NGLISH 4 way CASSETTE type 90x90 HTW MI45Q4DHN1D HTW MI56Q4DHN1D HTW MI71Q4DHN1D HTW MI80Q4DHN1D HTW MI100Q4DHN1D HTW MI140Q4DHN1D Thanks for choossing our product Please read carefully this manual be...

Page 2: ...ust be properly arranged so that control board cover is fixed properly If control board cover is not fixed perfectly it will cause heat up at connection point of terminal fire or electrical shock If t...

Page 3: ...er Do not connect the ground wire to gas or water pipes lightning rod or a telephone ground wire Incomplete grounding may result in electric shocks Be sure to install an earth leakage breaker Failure...

Page 4: ...k 6 Connective pipe for restriction assembly 7 Soundproof insulation sheath 8 Out let pipe sheath 9 Out let pipe clasp 10 Tightening band 16 Remote contronller owner s manual 17 Installation manual 13...

Page 5: ...oil permeates G Place where strong electromagnetic waves exist H Place where flammable gases or materials exist I Place where acid or alkali gases evaporate J Other special environments 1000mm 1000mm...

Page 6: ...d cables To balance the ceiling and to avoid vibration please enforce the ceiling when necessary Adjust the hexangular nuts on the four installation hooks evenly to ensure the balance of the body Sele...

Page 7: ...iling Main body Hexagon nut For adjust to balance Drain pipe Electrical restricting assembly Main body of the unit Ceiling Indoor unit model 8000W 9000W NOTE All the pictures in this manual are for ex...

Page 8: ...ial is the high quality carbon steel galvanized or covered other rust preventive materials on the surface or rustless steel The ceiling rust prevention measure is conducted according to actual constru...

Page 9: ...ay motor Hook bolt Sway motor Drain pipe joint Water receiver hook Panel hook Piping joint panel sponge body Ceiling panel panel foam1 air out Fan panel foam 2 4 6 m m outlet foam Fig 4 16 Fig 4 15 1...

Page 10: ...on duct In case of one duct connection The air volume in duct is around 300 360m3 h for 5600W to 8000W unit The air volume in duct is around 400 640m3 h for 9000W to 15500W unit The max length of duct...

Page 11: ...backflow into unit inside during shutdown the drain pipe shall place down side and drain water to outdoor drain side the gradient of the drain pipe should be higher than 1 100 without salient and wate...

Page 12: ...n malfunction occur During normal operation please ensure that this plug is stuffed tightly to prevent water leakage 6 INSTALL THE CONNECING PIPE 6 1 The connective length of indoor and outdoor piping...

Page 13: ...onnection wires Use wrapping tape to tie them tight Do not let air penetrate into it lest condensation and drips of moist 3 Pull the connective wrapped connective pipe from outdoor through the sheath...

Page 14: ...d with external grounding wire reliable 2 Electric wiring must be done by professionals and wiring according to the wiring label 3 Fixing circuit must be wired with an a11 poledisconnection device at...

Page 15: ...wire Please apply the attached thermal insulation material to seal the jointing part of the pipe Failure sealing would lead to condensation 7 6 Wires in panel Wire the wires holder of swinging motor...

Page 16: ...nit there is no need to control indoor unit separately for details please refer to V4 outdoor unit manual 3 For previous control of indoor units the network can be set by connecting X Y E terminals th...

Page 17: ...wn the unit for cold wind proof 00 means the time of stopping TERMAL fan is 4 minutes 01 means the time of stopping TERMAL fan is 8 minutes 10 means the time of stopping TERMAL fan is 12 minutes 11 me...

Page 18: ...stop valves are both opened The air conditioner is pre heated by turning on the power Set the air conditioner under the mode of COOLING with the remote controller and check the following points If th...

Page 19: ...C Industria 13 l Pol gono Industrial El Pedregar 08160 Montmel Barcelona Spain Phone 0034 93 390 42 20 Fax 0034 93 390 42 05 info htwspain com www htwspain com...

Reviews: