H. Applications

Figure 4 - Piping Detail - NOTE: Drawing is meant to demonstrate system 

piping concept. Heat traps are optional.

PIPING NOTES:

The following notes are applicable to all of the piping applications 

demonstrated on this page.

1. Minimum pipe size should match connection size. Upsize pipe 

accordingly if greater flow is required.

2. A thermal expansion tank suitable for potable water must be 

sized and installed within this piping system between the backflow 

preventer and the cold water inlet.

3. All circulators should have an integral flow check.

4. Drains and check valve between unit and storage tank will assist in 

purging air from system.

5. These drawings are meant to demonstrate system piping only. The 

installer is responsible for all equipment and detailing required by 

local codes. In Massachusetts, you must install a vacuum relief valve 

per 248 CMR.

6. Mixing valve application is optional, but recommended to help 

prevent scalding. See Part 3 for more information.

Part 4 - Wiring

This unit is factory wired to a junction box on top of the water heater 

for field wiring connection. These heaters are equipped and wired 

for the maximum possible input allowable (see Table 3 for listing of 

inputs and amperage requirements). The voltage requirement and 

dedicated wattage load for the heater is specified on the rating label 

of the water heater. Consult your local power company to determine 

if your electrical service is adequate for the additional load of the 

heater.

Refer to the wiring diagrams for field connections. All wiring must 

conform to local code and the National Electric Code, and should be 

done by a qualified licensed electrician or the local electric utility. 

Grounding can be accomplished by using approved conduit and 

fittings or other approved conductive material. A grounding wire is 

provided on the junction bracket. This grounding wire must be used 

in the installation.

Tank must be full of water before the power is turned on. Heating 

elements will be damaged if energized for even a short time 

while tank is dry. Failures due to “dry-firing” ARE NOT covered by 

warranty.

Be sure to ground the water heater. The preferred way to ground 

is with rigid metal conduit between the main panel and the water 

heater junction box with approved end fittings (check codes on 

the use of flexible conduit). If making a separate ground, a green 

ground wire is provided in the water heater junction box. Replace 

the junction box cover and insulation after you have made the 

wiring connections. Failure to follow these instructions could 

result in property damage, severe personal injury, or death.

Figure 5 - Sealing the Water Heater for Sanitary Applications

Summary of Contents for Everlast C2X030

Page 1: ...iable for typographical errors in literature NOTE TO CONSUMER PLEASE KEEP ALL INSTRUCTIONS FOR FUTURE REFERENCE 272 Duchaine Blvd New Bedford MA 02745 www htproducts com lp 565 Rev 002 Rel 005 Date 11...

Page 2: ...nnect only to a properly grounded outlet See Part 4 Wiring this manual for grounding details 3 Install or locate this water heater only in accordance with the provided installation instructions 4 Use...

Page 3: ...rt 8 Troubleshooting 15 Limited Warranty 16 Customer Installation Record Form 18 Do not use this water heater for anything other than its intended purpose as described in this manual Doing so could re...

Page 4: ...the water heater as centralized to the piping and electrical system as possible Also locate the water heater and domestic water piping where it will not be exposed to freezing temperatures All piping...

Page 5: ...onal more frequent maintenance may be required If you suspect that your water is contaminated in any way discontinue use of the appliance and contact an authorized technician or licensed professional...

Page 6: ...69 23 1 4 8 UL 1453 3 4 NPT 151 120oF 48 8 C 181oF 82 8 C 200oF 93 3 C EVC100 100 7 1 4 52 61 27 206 EVC115 115 60 1 4 69 224 Table 2 Specifications and Dimensions Refers to Electrical Specifications...

Page 7: ...n Figure 3 for the electric water heater to operate properly Failure to install these fittings properly will result in improper water heater operation possible substantial property damage and increase...

Page 8: ...the water heater and check valve and must be sized for the entire water volume of the hot water system See piping Applications Other methods of controlling thermal expansion are available Check with t...

Page 9: ...RE TO RE INSPECT THE T P VALVE AS DIRECTED COULD RESULT IN UNSAFE TEMPERATURE AND OR PRESSURE BUILD UP WHICH CAN RESULT IN PROPERTY DAMAGE SERIOUS PERSONAL INJURY OR DEATH Do not thread a cap or plug...

Page 10: ...perage requirements The voltage requirement and dedicated wattage load for the heater is specified on the rating label of the water heater Consult your local power company to determine if your electri...

Page 11: ...Heating elements will be damaged if energized for even a short time while tank is dry Failures due to dry firing ARE NOT covered by warranty A Combination Thermostat and High Limit Control ECO After...

Page 12: ...attempting heating element replacement will result in property damage severe personal injury or death due to electric shock STEP 2 Run hot water at a faucet in the system When it runs cold shut off th...

Page 13: ...ter faucet s once all air has been bled from the system when water runs freely Make certain that the heater is completely full of water before restoring power Periodically At least twice a year Check...

Page 14: ...ve operation and possibly result in substantial property damage severe personal injury or death 9 10 14 16 1 3 4 5 6 7 7 8 8 8 10 11 12 13 15 9 16 T R A P N O I T P I R C S E D M E T I 1 JUNCTION BOX...

Page 15: ...thermostat setting or replace 3 Tighten wire connections Improper wiring Check and rewire per Wiring Detail Not Enough Hot Water Heater undersized Reduce rate of heater use Defective element s Check a...

Page 16: ...er heater shall then be deemed to have commenced on the date of manufacture of the water heater and NOT the date of installation of the water heater and be covered by the unexpired portion of the Stan...

Page 17: ...hase of the product or an original certificate of occupancy for a new home 2 Clear pictures or video of the following a Serial number tag sticker b The product c The product issue failure whenever pos...

Page 18: ...allation Installation Address Product Name Serial Number s Comments Installer s Code Name Installers Phone Number Signed by Installer Signed by Customer Installation Notes IMPORTANT Customer Please on...

Reviews: