background image

LP-743 Rev. 000 Rel. 000 Date 8.25.20

8

3. Wiring a Cascade System
NOTE:

 Disconnect the WiFi PCB on each Follower boiler prior to setting 

up the cascade system. Only the Master boiler should be connected 

to WiFi. 

NOTE:

 Use the Establishing Boilers as Masters and Followers procedure, 

outlined in Part 2, when connecting boilers together on the BUS.

Failure to follow these instructions will result in improper system 

operation, wasted time, money, and possible property damage 

and personal injury. Such damages ARE NOT covered by product 

warranty.

CN1

Cascade 

Connection

Outdoor

Sensor

Tank temp. 

probe

System

Sensor

Room Thermostat

1

2

3

4

5

6

7

BUS

T B

5V IN

OD TNK

SYS TT1

TT2

120V

120V 120V

120V

120V 120V

Figure 7 - Low Voltage Wiring Connections

Ensure cascade wiring between boilers always runs from the 

BUS “T” connection to the next BUS “T” connection, and BUS “B” 

connection to the next BUS “B” connection. “T” to “T”; “B” to “B”.

NOTICE

Take care to route the BUS communication cables and other low 

voltage wiring away from line voltage cables to avoid electrical 

interference which can cause operation issues or damage the main 

PCB.

Master Boiler Low Voltage Wiring

BUS

BUS Network - Communication between cascaded boilers 

(up to 8) and/or HTP Room Sensors (up to 3) and/or one 

HTP Multifunctional Kit. Maintain correct polarity of “B” 

and “T” terminals. Use a minimum of 20 AWG cable, prefe-

rably twisted pair, up to a maximum of 164 feet.

TT2

Room Thermostat 2 - Dry contact input for System CH 

Zone 2 demands. Parameters 5.1.0 through 5.7.5 are 

applicable to Zone 2 demands. 

NOTE:

 Zone 1 (TT1) demands take priority over Zone 2 

(TT2) demands.

OD

Outdoor Sensor - Connect to factory provided outdoor 

sensor to allow Automatic CH Temperature Control (or 

connect Master boiler to WiFi and use Internet Weather).

TNK

Tank Sensor or Aquastat - Connect to a tank sensor or 

Aquastat installed in a Downstream IWH heated by the 

entire cascade system and set via 25.2.2. Or, installed in 

an Upstream IWH connected to the Master boiler and set 

via 2.2.8.

NOTE: 

The Master boiler cannot heat both a Downstream 

and an Upstream IWH.

NOTE:

 If 25.2.2 = 1 or 2, the Master boiler considers the 

IWH to be Downstream and uses the entire cascade to 

service it - regardless of the setting of parameter 2.2.8.

SYS

System Sensor – Connect to a system sensor installed on 

the supply line of the secondary loop – DO NOT INSTALL 

IN PRIMARY LOOP.

NOTICE: 

Failure to install a system sensor will cause the 

cascade system to operate in Emergency Mode.

TT1

Room Thermostat 1 – Dry contact input for System CH 

Zone 1 demands.  Parameters 4.1.0 through 4.7.5 are 

applicable to Zone 1 demands.  

NOTE: 

Zone 1 demands (TT1) take priority over Zone 2 

(TT2) demands.

Follower Boiler Low Voltage Wiring

BUS

BUS Network - Communication between cascaded 

boilers (up to 8) and/or HTP Room Sensors (up to 3) or 

one HTP Multifunctional Kit. Maintain correct polarity of 

“B” and “T” terminals. Use a minimum of 20 AWG cable, 

preferably twisted pair, up to a maximum of 164 feet.

TT2

Auxiliary Limit Switch Input – Input does not function as 

a CH Zone 2 input, but functions as a limit switch input 

with parameter 34-40.2.3 = 0. 

OD

Not Applicable - Input does not function on Follower 

boilers.

TNK

Tank Sensor or Aquastat - Connect to a tank sensor or 

Aquastat installed in an Upstream IWH connected to 

the respective Follower boiler. Set to Tank Sensor or 

Aquastat via parameter 34-40.2.8.

SYS

Not Applicable - Input does not function on Follower 

boilers.

TT1

Not Applicable - Input does not function on Follower 

boilers.

Figure 6 - Access to Low Voltage Wiring Connections

Summary of Contents for EFTU Series

Page 1: ...er birth defects or other reproductive harm The surfaces of these products contacted by potable consumable water contain less than 0 25 lead by weight as required by the Safe Drinking Water Act Section 1417 Heat Exchanger Bears the ASME H Stamp This document is provided in addition to other documentation and DOES NOT REPLACE the installation manual This document must only be used by a qualified in...

Page 2: ...tream of all closely spaced tees 4 The minimum individual boiler pipe size of DHW piping should be diameter and CH piping should be 1 in diameter 5 Circulators are shown with isolation flanges The alternative is standard flanges with full port ball valves Purge valves can be used with circulator flanges as an alternative 6 Piping shown is Primary Secondary 7 Install a minimum of 12 diameters of st...

Page 3: ...NCTION BOX BUS T B 120V TT2 120V OD 5V IN 120V TNK 120V SYS 120V TT1 120V PCB CONTROL PANEL RT DHW PUMP CH PUMP 120VAC JUNCTION BOX OD OD MASTER FOLLOWER RT FOLLOWER DOWNSTREAM INDIRECT FIRED WATER HEATER UPSTREAM INDIRECT FIRED WATER HEATER Piping for Models ELU 85WBN 120WBN 120WCN 150WCN NOTICE In this plumbing application parameter 25 1 6 needs to be adjusted to setting 1 This ensures the CH pu...

Page 4: ...PUMP CH PUMP 120VAC JUNCTION BOX RT DHW PUMP CH PUMP 120VAC JUNCTION BOX RT OD OD MASTER FOLLOWER FOLLOWER DHW PUMP CH PUMP 120VAC JUNCTION BOX DOWNSTREAM INDIRECT FIRED WATER HEATER UPSTREAM INDIRECT FIRED WATER HEATER Piping for Models ELU 150WBN 199WBN 199WCN EFTU 85WBN 110WBN 150WBN 199WBN 110WCN 150WCN 199WCN NOTICE In this plumbing application parameter 25 1 6 needs to be adjusted to setting...

Page 5: ...ishing Boilers as Master and Followers procedure Menu level 25 is not accessible unless 0 4 6 is set to b MAS Parameter Description Value Default Setting 0 4 6 Cascade Boiler Address Master boiler must be set to b MAS UNDEF undefined b SIN single boiler b MAS master boiler b FL1 Follower 1 boiler b FL2 Follower 2 b FL3 Follower 3 b FL4 Follower 4 b FL5 Follower 5 b FL6 Follower 6 b FL7 Follower 7 ...

Page 6: ...er Menu Refer to parameter 5 2 5 and 6 2 5 for CH Zone 2 and 3 4 2 6 Minimum CH Temperature Setting Zone 1 TT1 68 122 F when 4 2 0 0 86 179 F when 4 2 0 1 80 4 2 0 0 120 4 2 0 1 Sets the minimum allowable boiler operating temperature for CH Zone 1 limiting Automatic Temperature Control and manual adjustment from the User Menu Refer to parameter 5 2 6 and 6 2 6 for CH Zones 2 and 3 25 1 6 System CH...

Page 7: ...ting Power 120V for DHW and CH Circulators NOTE TheCHanddownstreamIWHcirculatorsMUSTBECONNECTED to the Master Boiler to ensure proper operation To connect power for the CH and DHW external pump at the boiler junction box 1 Shut off the power supply at the boiler and at the circuit breaker 2 Shut off the gas at the manual shutoff 3 Remove the boiler front cover 4 Disconnect the three clips and open...

Page 8: ... allow Automatic CH Temperature Control or connect Master boiler to WiFi and use Internet Weather TNK Tank Sensor or Aquastat Connect to a tank sensor or Aquastat installed in a Downstream IWH heated by the entire cascade system and set via 25 2 2 Or installed in an Upstream IWH connected to the Master boiler and set via 2 2 8 NOTE The Master boiler cannot heat both a Downstream and an Upstream IW...

Page 9: ...by Boiler Supply Sensor Master Homescreen 3 Boiler Supply Temperature This screen displays the current temperature read by the master boiler supply sensor 150oF is displayed below Figure 11 Master Homescreen 3 Boiler Off This screen displays if the master boiler is turned off with the ON OFF button Master Homescreen 4 Cascade Master Operating Power Level This screen displays the current operating ...

Page 10: ...iler Operating Power Level This screen displays the current operating power level percentage of the follower boiler A power level of 40 is displayed below PL Denotes Boiler Power Level Current Power Level Percentage Figure 18 Follower Homescreen 3 Boiler Power Level Follower Homescreen 4 Indirect Water Heater Tank Temperature Aquastat Status of Upstream Local IWH This screen is only displayed on t...

Page 11: ...0 Setpoint 16 Service 1 S W Changeover 17 Error History 2 Z3 Settings 18 Free Parameters 3 Z3 Diagnostics 42 BMS Parameters 7 Z3 Regulation parameters 0 General 8 Service Parameters 1 Analog Level Settings 0 Boiler Statistics 1 2 Diagnostics 1 Boiler Statistics 2 2 Boiler 3 Boiler Temperature 4 Storage 5 Service 6 Error History 7 Free parameters 8 Reset Factory Settings 9 Other 1 10 Other 2 11 HTP...

Page 12: ...ctory Settings 9 Other 1 10 Other 2 11 Boiler Statistics 1 12 Boiler Statistics 2 13 Boiler 14 Boiler Temperature 15 Storage 16 Service 17 Error History 18 Free Parameters 19 20 28 29 31 32 33 34 47 53 Boiler Temperature Quick Access Menus PCB Direct Access to the Parameters 34 40 19 34 40 20 34 40 28 34 40 29 34 40 31 34 34 40 47 34 40 53 ERR Fault The display shows the last 10 errors with the co...

Page 13: ...void short cycling ensure 25 0 4 is set to less than half of 25 0 5 setting Applicable only when parameter 25 0 2 0 25 0 5 Cascade Manager Max Turnover Level par 25 0 4 100 70 Sets the power level threshold where the next boiler is switched on Switches on if required power is 25 0 5 Switches off if required power is 25 0 5 25 0 3 Off logic only applicable if parameter 25 0 2 1 25 0 7 CH On Differe...

Page 14: ... and CH will not operate simultaneously Priority switches between DHW and CH at an interval de fined by the CH DHW Shifting Priority Time parameter 25 0 8 first priority is DHW If 25 0 8 0 then DHW has priority indefinitely 1 Timed Concurrent Alternating DHW and CH operate simultaneously for the period defined by the CH DHW Shi fting Priority Time parameter 25 0 8 After the time elapses operation ...

Page 15: ...LER 1 7 34 40 0 GENERAL 34 40 0 1 DHW Preheating 0 Disabled 1 Enabled 1 Enables disables DHW Comfort Function on WCN models not applicable to WBN models See par 25 2 1 34 40 1 FREE PARAMETER 34 40 1 9 DHW Flow Detection Device Type 0 Flow Switch 1 Flow Meter Varies Default 0 for TRX085 120 110C 150C Default 1 for TRX150 199 199C FTVN085 110 150 199 110C 150C 199C WCN models use a flow meter Not ap...

Page 16: ...ring 34 40 5 3 DHW Switch Off Logic 0 anti scale stop at 144 F 1 7 F setting 0 34 40 5 4 DHW Post Purge and Pump Cycle 0 OFF 1 ON 1 OFF 30secondpost circulationand2minutepost ventilation or3minutepost circulationand5minutepost ventilation if the boiler temperature requires it ON When setting is ON time for post circulation is 3 minutes while the time for post ventilation is 5 minutes Default 0 for...

Page 17: ...40 10 OTHERS 2 34 40 10 0 NOT USED 34 40 10 1 DHW Modulation Setpoint 68 179oF 179 Boiler target temperature during a DHW demand Not applicable for WCN models 34 40 10 2 DHW On Differential Temperature 0 36oF 0 Determines how much the DHW storage tank temperature can drop below target before initiating a DHW demand Only applicable when 2 2 8 1 34 40 10 3 Emergency Setpoint 68 179oF 113 Sets Follow...

Page 18: ...xt maintenance 0 60 months 12 If enabled 8 5 1 1 a notification is made on the display and via the Tele diagnostic Service if applicable warning that it is time for maintenance 34 40 55 1 Enable Maintenance Warning 0 OFF 1 ON 0 34 40 55 2 Maintenance Warning Reset Reset OK Yes Esc No Resets Maintenance Advice and clears the Warning 34 40 55 4 SW Version Display Interface 34 40 55 5 SW Version Main...

Page 19: ...address Press OK again 2 If above process does not work access parameter 0 4 6 and set the correct boiler address see Cascade Control Set Up Blocking Auto Reset EMERG Emergency Mode 1 The Follower has been disconnected from the BUS or no longer sees the Master on the BUS check the BUS connections See Wiring a Cascade System 2 The control has sensed a short circuit on the BUS connection Disconnect ...

Page 20: ...LP 743 Rev 000 Rel 000 Date 8 25 20 20 Maintenance Notes ...

Reviews: