background image

lp-548 Rev. 000 Rel. 004 Date 1.11.19

3

CAUTION

Use the mounting template and screws provided with the adapter. Damage to the MODBUS/BACnet adapter or appliance due to installation 

with other mounting screws IS NOT covered by warranty.

When mounting the unit, keep in mind that the top cover must be removed to connect the RS-485 communication cable, and that the 

appliance communication wire must reach the control inside the appliance. 

The MODBUS/BACnet adapter can be mounted on the side of the appliance OR the wall next to the appliance, as long as care is taken to avoid 

components behind the mounting surface. The mounting location must be within 3 feet of the appliance controller in order to be plugged 

into the controller input port.

In BIC-926 based appliances, the four pin connector from the adapter must be plugged into the white connector labeled X3 on the 

control. 

In BIC-928 based appliances, the four pin connector from the adapter must be plugged into the black connector labeled X4 on the 

control.  

In both cases the adapter end of the four pin cable MUST be plugged into the BLACK connector labeled BIC X3 of the adapter circuit 

board!

NOTE:

 It is not recommended to install the MODBUS/BACnet adapter inside the appliance housing. Doing so may affect appliance operation 

or damage the MODBUS/BACnet adapter.

A. BMS Wiring Requirements

RS-485 Communication Bus

• 

Maximum length: 4000 

feet

• 

Cable specification: 24 

AWG / A,B (twisted pair) 

and GND shielded, with 

characteristic impedance: 

120 ohm

• 

Maximum load: 32 units 

(32 nodes)

Wires will be passed through the 

PG connector on the side of the 

adapter, then connected to the 

three position connector marked 

“X5” on the circuit board inside the 

adapter. A label is provided inside 

the adapter to ensure proper 

connections of A, B, and GND. Two 

wires (MB IN and MB OUT) may be 

attached to each X5 screw.

See Figure 3 for an example wiring 

diagram.

Figure 3 - Jumper Configurations in a MODBUS / BACnet Network

CAUTION

Damage to MODBUS/BACnet adapter or appliance due to improper installation IS NOT covered by warranty.

B. Jumper Setting

The appliance display handles 

most of the MODBUS/BACnet 

adapter configuration. There is 

one jumper on the MODBUS/

BACnet adapter. When this jumper 

is in place (factory default) it 

connects a termination resistor 

across the data lines of the RS-485 

connection. Leave the jumper in if 

the MODBUS/BACnet adapter is at 

the end of the RS-485 bus. Remove 

the jumper if the MODBUS/

BACnet adapter is one of many 

connections and not at the end of 

the bus. See Figures 3 and 4.

Figure 4 - MODBUS Termination Jumper Location (Highlighted in Grey)

Summary of Contents for 7350P-636

Page 1: ...s or to important product information CAUTION used without the safety alert symbol indicates a potentially hazardous situation which if not avoided may result in property damage Table of Contents Part 1 General Information 2 A What s in the Box 2 B Minimum System Requirements 2 C Definitions 2 Part 2 Installation 2 A BMS Wiring Requirements 3 B Jumper Setting 3 Part 3 Communication Configuration 4...

Page 2: ... protocol developed by AEG Modicon Baud Baud Rate Number of data bits transmitted per second bps MSB Most Significant Byte BMS Building Management System RS232 RS232 serial full duplex FDX transmission of data standard EMS Energy Management System RS485 RS485 serial transmission of data standard FDX Full Duplex RTU Remote Terminal Unit HDX Half Duplex PG Industry Standard liquid tight wiring entry...

Page 3: ...S BACnet adapter inside the appliance housing Doing so may affect appliance operation or damage the MODBUS BACnet adapter A BMS Wiring Requirements RS 485 Communication Bus Maximum length 4000 feet Cable specification 24 AWG A B twisted pair and GND shielded with characteristic impedance 120 ohm Maximum load 32 units 32 nodes Wires will be passed through the PG connector on the side of the adapter...

Page 4: ...h the RS485 address of 31 will have a device ID of 600031 NOTE MODBUS must be enabled on the appliance as outlined above for the following parameters to be viewed and changed The BACnet address space is comprised of 256 addresses These are defined as follows Address 255 is a broadcast address The master can send data to address 0 and all followers will process the data Addresses 0 127 are free to ...

Page 5: ... 5 Final Baud Rate Settings E Parity and Stop Bits NOTE This setting only applies to MODBUS operation The BACnet protocol does not utilize parity for communication and this setting will have no effect The parity stop bits parameter of the MODBUS BACnet adapter must be set to match the rest of the devices on the bus Although it is common to set serial devices to use no parity setting the parity to ...

Page 6: ...XCEPT Versa Hydro Alarm output BI 33 1 on 0 off 1 10035 CH pump 1 N A BI 34 1 on 0 off 1 10036 DHW pump 1 N A BI 35 1 on 0 off 1 10038 Gas valve 1 Gas valve BI 37 1 on 0 off 1 10039 Sys pump N A BI 38 1 on 0 off 1 10049 Boiler 1 Run same as 11118 Run status BI 48 1 on 0 off 1 10050 Boiler 2 Run same as 10023 N A BI 49 1 on 0 off 1 10051 Boiler 3 Run N A BI 50 1 on 0 off 1 10052 Boiler 4 Run N A BI...

Page 7: ...utlet 3 N A AI 25 Deg F 0 1 30027 Boiler 3 Firing Rate N A AI 26 1 30028 Boiler 3 Status N A AI 27 N A 1 30029 Boiler 3 Lockout N A AI 28 N A 1 30030 Boiler Outlet 4 N A AI 29 Deg F 0 1 30031 Boiler 4 Firing Rate N A AI 30 1 30032 Boiler 4 Status N A AI 31 N A 1 30033 Boiler 4 Lockout N A AI 32 N A 1 30034 Boiler Outlet 5 N A AI 33 Deg F 0 1 30035 Boiler 5 Firing Rate N A AI 34 1 30036 Boiler 5 St...

Page 8: ...Table 8 MODBUS and BACnet Memory Map Only Valid Valves During Heating Cycle Address 40001 AV0 contains configuration bits sent from the BMS to the appliance These bits tell the appliance to use its own internal inputs or inputs from the BMS When a bit is set to 1 the appliance will ignore the corresponding value contained internally and expect the BMS to write that value into the holding registers...

Page 9: ...rs Definition Decimal Value HEX Value Action 40001 AV0 Configuration 3 0011 Set configuration to read 40002 40002 AV1 Coils 1 0001 Enables CH Demand 00 00 disables demand boilers only 40002 AV1 Coils 16 0010 Enables DHW demand on appliance 00 00 disables demand 40002 AV1 Coils 17 0011 Enables both CH and DHW demand DHW demand will have priority Table 10 Example 1 Holding Registers Definition Decim...

Page 10: ...with the setpoint controlled by the 600 menu parameter CENTRAL HEAT on appliances or the PHOENIX setting in the water heater user menu If the command value is anywhere between 16 and 100 the appliance will run at a setpoint proportional to the command sent between minimum and maximum setpoints NOTE To ensure proper operation resend the configuration bits to holding register 40001 AV0 prior to issu...

Page 11: ... the typical installation with a hot water generator in close proximity to the appliance with the tank thermostat or tank temperature sensor wired to the terminal strip or Customer Connection Board of the appliance DHW with Remote Control This installation may or may not have the hot water generator in close proximity to the appliance Its sensors and thermostat values are only available through th...

Page 12: ... No Burner Control Communication 0 5 seconds on 1 5 seconds off No MODBUS BACnet Communication 1 5 seconds on 0 5 seconds off Figure 7 MODBUS BACnet Diagnostic LEDs B Physical Layer 1 Adapter and Serial Port a Ensure adapter is plugged into the correct four pin connector i It plugs into the WHITE connector on the BIC 926 control ii It plugs into the BLACK connector on the BIC 928 control C Communi...

Page 13: ...19 Water Low 2 34 None 5 Blocking Temperature 20 Water High 2 35 Service Pump 6 DHW Function Internal 21 CH On Off Thermostat 40 Lockout 7 DHW Function Internal 22 CH Zone Demand 51 Frost Protection Pump 8 DHW Indirect 23 CH Cascade Demand 52 Frost Protection Burner 9 DHW Direct 24 CH Pool Demand 60 Summer Kick 10 DHW Phoenix 25 CH 61 Save EEPROM Blocking 11 DHW Spa 26 CH 96 Running 12 DHW 27 CH 1...

Page 14: ...ing 186 ECS7 Temperature Lockout 233 F09 No Flame After Ignition 190 F05 S1 Maximum Temperature 235 APS Stuck Closed 191 F06 S2 Maximum Temperature 236 APS Stuck Open 192 S1 Shorted 237 F11 False Flame 193 F02 S1 Interrupted 239 F01 Safety Thermostat Open 194 S2 Shorted 240 F00 Flue Thermostat Open 195 S2 Interrupted 241 External LWCO 196 Low Water Lockout 243 Gas Pressure 197 Flue Sensor Shorted ...

Page 15: ...ty Wizard http www htproducts com Warranty Wizard html to check warranty eligibility You may also contact HTP Technical Support at 1 800 323 9651 for questions or assistance Warranty coverage requires review and approval of the issue with HTP Technical Support or through the Warranty Wizard prior to a full unit replacement Any claim for warranty reimbursement will be rejected if prior approval fro...

Page 16: ...lp 548 Rev 000 Rel 004 Date 1 11 19 16 Installation and Maintenance Notes ...

Reviews: