background image

15 

 

HOLDING REGISTER 40001 

DEFINITION 

0 = TAKEN FROM CONTROL 

1 = TAKEN FROM MODBUS 

B0 

Boiler enable 

0/1 

B1 

Tank enable 

0/1 

B2 

Rate command / 0 

– 10V input / set point command (40003) 

0/1 

B3 

DHW set point (40004) 

0/1 

B4 

DHW temperature (40005) 

0/1 

B5 

Outdoor temperature (40006) 

0/1 

B6 

System supply temperature (40007) 

0/1 

B7 

System return temperature (40008) 

0/1 

B8 

I4 offset (40009) 

0/1 

B9 

CH post purge (40010) 

0/1 

HOLDING REGISTER 40001 

DEFINITION 

0 = TAKEN FROM CONTROL 

1 = TAKEN FROM MODBUS 

B10 

DHW post purge (40011) 

0/1 

B11 

Pump 4 speed (40012) 

0/1 

B12 

Pump 5 speed (40013) 

0/1 

B13 

Extra 0 

– 10 V output (40014) 

0/1 

HOLDING REGISTER 40002 

DEFINITION 

 

Coil 01 b0 

Room thermostat 

 

Coil 05 b4 

Tank thermostat 

 

Table 14 

– Modbus holding registers 

PART 7 - APPLIANCE OPERATION 

A. APPLIANCE OPERATION WITH MODBUS COMMUNICATIONS 

The appliance is equipped with a Modbus communication timer. Timeout is set for four minutes. The purpose of the timer is to ensure 
proper temperature data is communicated to the appliance in a timely manner. 
 
Additionally, the communication timer will provide fail safe operation should Modbus communication be lost. This timer will cause the 
appliance to revert back to internal appliance controls should the Modbus communication be interrupted longer than the Modbus timer. 
The timer resets every time a Modbus write command is received with updated temperatures or commands. 
 
The master should update temperature registers at least once per minute, but no more than once per second. 

B. EXAMPLE #1 

In this configuration, the appliance is controlled by setting the set points locally on the appliance and providing an enable signal through 
Modbus communications. 
 
All sensors and limiting devices (excluding the thermostat enable and tank thermostat enable signals, which will be sent to the 
appliance via Modbus) should be hardwired to the proper terminals in the appliance. 
 
The holding registers need to be set as follows: 
 

HOLDING REGISTERS 

DEFINITION 

VALUE 

ACTION 

40001 

Configuration 

00 01 

Set configuration to read 40002 

40002 

Coils 

00 01 

Enables CH Demand 

(00 00 disables demand)

 

40002 

Coils 

00 10 

Enables DHW demand on appliance (00 00 disables demand) 

40002 

Coils 

00 11 

Enables both CH and DHW demand. DHW demand will have priority 

Table 15 

C. EXAMPLE #2 

1. SEND FIRING RATE COMMAND FROM MASTER 

In this configuration, the appliance is controlled by setting the modulation set point from 0 

– 100%. Rate command will be 0 – 100% of 

the modulation range. All sensors and limiting devices (excluding the 0 

– 10 Vdc signal, which will be sent to the Modbus) should be 

hardwired to the terminal strip on the back of the appliance. 
 
For this command to function on Munchkin and Mod Con models, set Installer Parameter 16 at 2 and Installer Parameter 17 at 1. On 
Elite models, Function 16, Optional Input must be set to 0-10 volt and Function 17 0-10 volt function must be set on Temperature. 
 
The holding registers need to be set as follows: 
 

Summary of Contents for 7350P-629

Page 1: ... WITH MODCON MODCON VWH PIONEER VERSA FLAME MANUFACTURED ON OR AFTER JULY 1 2011 FOR USE WITH ELITE ELITE VWH MANUFACTURED ON OR AFTER AUGUST 1 2011 NOTICE HTP reserves the right to make product changes or updates without notice and will not be held liable for typographical errors in literature NOTE TO CONSUMER PLEASE KEEP ALL INSTRUCTIONS FOR FUTURE REFERENCE ...

Page 2: ...iances FOR THE INSTALLER The installer should be guided by the instructions furnished with the Modbus local codes and utility company requirements Preference should be given to codes and requirements where they differ from the furnished instructions Additional publications which should guide the installer include The latest version of the National Electrical Code NFPA No 70 In Canada refer to Cana...

Page 3: ...ROM MASTER 16 D EXAMPLE 3 HOT WATER GENERATION 16 E CASCADE 16 F RATE AND TEMPERATURE CONVERSIONS 17 G APPLIANCE STATUS CODES 19 PART 8 TROUBLESHOOTING 19 A PHYSICAL LAYER 19 B COMMUNICATIONS 19 C LED DIAGNOSTICS 19 D MODBUS ERROR CODES 19 INSTALLATION AND MAINTENANCE NOTES 20 HTP CUSTOMER INSTALLATION RECORD FORM 21 PART 1 GENERAL INFORMATION Modbus communication systems utilize a master follower...

Page 4: ... heater equipped with a control with firmware revision MTSA P110414 or greater To determine whether your product is compatible with this adapter refer to Figure 1 3 Shielded twisted pair communication cable Figure 1 Controller Revision Label Location C DEFINITIONS Table 1 is a list of definitions used throughout this manual ABBREVIATION OR ACRONYM DEFINITION ASCII American Standard Code for Inform...

Page 5: ...n be mounted on the side of the appliance OR the wall next to the appliance as long as care is taken to avoid components behind the mounting surface The mounting location must be within 3 feet of the appliance controller in order to be plugged into the controller programming port NOTE It is not recommended to install the Modbus adapter inside the appliance housing Doing so may affect appliance ope...

Page 6: ...guration There is one jumper on the Modbus adapter When this jumper is in place factory default it connects a termination resistor across the data lines of the RS 485 connection Leave the jumper in if the Modbus adapter is at the end of the RS 485 bus Remove the jumper if the Modbus adapter is one of many connections and not at the end of the bus See Figures 2 and 3 Figure 3 Modbus Termination Jum...

Page 7: ... have a unique address It is not recommended to use 1 as an address as this is often the default address for various other Modbus devices that may be on the bus In order to keep track of addresses for future maintenance purposes record all device addresses in the Installation and Maintenance Notes section included in this manual SAVE THIS DOCUMENT IN A SECURE LOCATION FOR FUTURE REFERENCE To set t...

Page 8: ... OFF MODBUS DISABLED factory default 37 ON MODBUS ON 37 AUTOMATIC MODBUS AUTO enables automatic detection of a PC or Adapter Table 5 Parameter 37 Settings FUNCTION 37 Press ENTER once the desired setting is flashing on the display Once accepted the selection should not flash Please do not leave the Installer Menu Configure the Address Baud Rate and Parity settings described below B MODBUS ADDRESS ...

Page 9: ...SETTING TEXT DISPLAY PARITY STOP BITS 1 ST No parity 1 stop bit 2 ST No parity 2 stop bits E PA Even parity 1 stop bit O PA Odd parity 1 stop bit Table 6 Parameter 40 Settings FUNCTION 40 Press ENTER The STOP PARITY value will blink Use the UP and DOWN arrows to toggle between 1 ST 2 ST E PA and O PA Make your selection based on the table above Press ENTER again to select the STOP PARITY value and...

Page 10: ...d input registers 5 05 Force single coil 6 06 Preset single register 7 07 Read exception status 8 08 0 00 Diagnostic Return query data 1 01 Diagnostic Restart communication 2 02 Diagnostic Return diagnostic register 4 04 Diagnostic Force listen mode 10 0A Diagnostic Clear counters and diagnostic registers 11 0B Diagnostic Return bus message count 12 0C Diagnostic Return bus exception error count 1...

Page 11: ...d the request but will take a significant amount of time to process it This response prevents a timeout error 06 FOLLOWER DEVICE BUSY This is received when a follower device is busy processing a programmed command User should query this device at a later time 08 MEMORY PARITY ERROR The server or follower attempted to read a file but detected a parity error in the memory The user can retry the requ...

Page 12: ...ance 5 burning 0 1 on 0 off 0 1 1 10055 Appliance 6 burning 0 1 on 0 off 0 1 1 10056 Appliance 7 burning 0 1 on 0 off 0 1 1 10057 Appliance 0 lockout same as 10034 0 1 on 0 off 0 1 1 10058 Appliance 1 lockout same as 10042 0 1 on 0 off 0 1 1 10059 Appliance 2 lockout 0 1 on 0 off 0 1 1 10060 Appliance 3 lockout 0 1 on 0 off 0 1 1 10061 Appliance 4 lockout 0 1 on 0 off 0 1 1 10062 Appliance 5 locko...

Page 13: ...upply temperature 0 Deg F 76 266 0 1 30043 Appliance 6 firing rate 0 0 100 1 30044 Appliance 6 status 0 NA 0 65535 30045 Appliance 6 lockout code NA 0 65535 30046 Appliance 7 supply temperature 0 Deg F 76 266 0 1 30047 Appliance 7 firing rate 0 0 100 1 30048 Appliance 7 status 0 NA 0 65535 30049 Appliance 7 lockout code 0 NA 0 65535 30050 Discrete inputs 49 64 0 NA 0 65535 30051 NTC 6 temperature ...

Page 14: ...uring programming 207 Parameter EEPROM failure 190 S1 maximum temperature 191 S2 maximum temperature 192 S1 shorted 193 S1 interrupted 194 S2 shorted 195 S2 interrupted 196 Low water lockout 197 Flue sensor shorted 198 Flue sensor interrupted 199 Low water lockout 2 185 ECS6 temperature lockout 186 ECS7 temperature lockout Table 12 E STATUS CODES STATUS CODES INPUT REGISTERS 30014 30023 30028 3003...

Page 15: ...ures or commands The master should update temperature registers at least once per minute but no more than once per second B EXAMPLE 1 In this configuration the appliance is controlled by setting the set points locally on the appliance and providing an enable signal through Modbus communications All sensors and limiting devices excluding the thermostat enable and tank thermostat enable signals whic...

Page 16: ...re value of Installer Parameter 12 above When the command is 100 the boiler will run at maximum temperature CH temperature above If the command value is anywhere between 16 and 100 the boiler will run at a temperature proportional to the command sent between minimum and maximum temperatures described above NOTE To ensure proper operation resend the configuration bits to holding register 40001 prio...

Page 17: ...ters or some scientific calculators For example RATE HEX 0 00 20 14 45 2D 60 3C 80 50 95 5F 100 64 Table 18 Temperature Conversions To send a desired set point the hexadecimal value must be determined through linear interpolation of programmable parameters on the BMS setup menu BMS temperature set point at low analog input BMS temperature set point at high analog input These variables set the temp...

Page 18: ...7 27 130 3F 163 57 98 28 131 40 164 58 99 29 132 41 165 59 100 2A 133 42 166 5A Temperature The Modbus adapter passes temperature data to the appliance in degrees Fahrenheit Also to accommodate decimal places the decimal value must be divided by 10 The data sent over the Modbus is passed as an unsigned 16 bit integer This poses no problem unless the data becomes negative such as temperatures below...

Page 19: ...ateway BAS master 3 Check for broken wires 4 Check A B terminal connections 5 Check for terminating resistors 120 ohms at each end of the RS 485 bus only 6 Check all wire lengths Are any drops too long 7 Check proper shield grounding B COMMUNICATIONS 1 Verify controller is configured for MODBUS AUTO or ON 2 Check baud rate 9600 19200 3 Check parity 4 Check Modbus address 5 Check port setting on ma...

Page 20: ...mand 4 Check configuration bits for holding register 40001 5 Check commands and data for holding registers 40002 40007 INSTALLATION AND MAINTENANCE NOTES _________________________________________________________________________________________ ...

Page 21: ...ler s Code Name Product Serial Number s Modbus Adapter Address As Configured by the Installer Comments Installer s Phone Number Signed by Installer Signed by Customer IMPORTANT NOTES Customer Please only sign after the installer has reviewed the installation safety proper operation and maintenance of the system In the case that the system has any problems please call the installer If you are unabl...

Reviews: