LP-420 REV. 2.14.20 

SCREEN 

DESCRIPTION 

Function 52

 

 

Solar Mode

 

SOLAR   MODE   

ON                           52                       

When turned ON, this parameter enables solar function of the control. Default: OFF. 

Function 41

 

Solar DT Off 

 

 

SOLAR   DT   OFF 

o

F                          41                 

Determines when the solar pump turns off based on the temperature differential between the panel 

sensor and tank sensor. Factory default 5

o

F. (Range 1

o

F to 40

o

F). 

Function 42

 

Solar DT On 

 

 

SOLAR   DT   ON 

o

F                          42                 

Determines when the solar pump turns on based on the temperature differential between the panel 

sensor and tank sensor. Factory default 9

o

F. (Range 95

o

F to 185

o

F). 

Function 43

 

Startup Time Solar 

 

 

STARTUP TIME SOLAR 

1 Minute                   43                 

In drain back systems, the pump turns on for a period of time to charge the system. Factory default 1 

minute. (Range 95

o

F to 185

o

F). 

Function 44

 

Anti Cycle Solar 

  

ANTI  CYCLE  SOLAR 

5 Minutes                 44                 

Sets the solar pump delay from the time Solar DT On is satisfied. Factory default 5 minutes. (Range 95

o

to 185

o

F). 

Function 45

 

NHX Solar 

 

 

NHX   SOLAR 

OFF                         45                 

When turned ON, selects the large storage tank / NHX configuration. Factory default OFF. (When set to 

ON, Functions 46 and 47 apply.) 

Function 46

 

NHX DT Off 

 

 

NHX   DT   OFF 

o

F                          46                 

Sets the differential between the storage tank sensor and lower tank sensor at which the solar circulator 

pump turns off. Factory default 0

o

F. (Range 1

o

F to 40

o

F). 

Function 47

 

NHX DT On 

 

 

NHX   DT   ON 

ON                           47                 

Sets the differential between the storage tank sensor and lower tank sensor at which the solar circulator 

pump turns on. Factory default 0

o

F. (Range 1

o

F to 40

o

F). 

Function 50

 

Solar Pump Min 

  

SOLAR  PUMP  MIN 

3.0                           50                 

Determines the voltage to the solar pump at its lowest speed. Factory default 3.0 Volts. (Range 1 to 10 

Volts). 

Function 51

 

Solar Pump Max 

 

 

SOLAR  PUMP  MAX 

10.0                         51                 

Determines the voltage to the solar pump at its highest speed. Factory default 10.0 Volts. (Range 1 to 10 

Volts). 

Table 3 – Solar System Parameters 

STEP 5: SOLAR STATUS MENU 

The controller also has the ability to review solar system status. To access solar status screens, press 

 twice. Once the first value is 

displayed, press the 

 or 

 keys to access additional information. At any point you may press 

RESET

 to exit the solar status screens. 

 

SCREEN 

DESCRIPTION 

 0%  SOLAR      SOLAR               

 0%  FUEL 

This screen displays the actual percentage of energy obtained from both the solar and gas-fired burner of 

the Versa-Hydro combination appliance. 

Press the 

 key once. 

PANEL   140

o

F  SOLAR 

TANK       75

o

F

 

The top line of this screen displays the temperature at the solar collector (Tp), and the bottom line 

displays the temperature of the solar tank (Tt).

 

Press the 

 key once.

 

 0.0  GPM          SOLAR 

  12  BTU  PUMP  100% 

The top line of this screen displays the amount of flow measured at the flow meter. The bottom line 

displays the amount of BTU gain per day based on (Tp-Tf) and flow. This calculation resets at midnight 

each day. Pump % refers to the current percentage of the maximum solar pump speed. 

Press the 

 key once.

 

SUPPLY 174

o

F SOLAR     

RETURN  72

o

F PUMP ON

 

The top line displays the temperature at the tank outlet. The bottom line displays the temperature at the 

flow meter (Tf). Pump will display ON when solar pump is running, OFF when the pump is off. 

Table 4 – Solar Status Menu 

Fault Conditions: 

 

Fault Description 

Error Type 

Display Message 

1)  Pump Boost Never Achieves Flow 

Solar Blocking 

No Solar Flow 

2)  Panel Temperature Sensor Working Improperly or Panel Temperature is Higher 

than Parameter 

  Can Happen During No Operation 

  Use Pump Menu to Manually Run the Solar Pump and Cool the Solar Loop 

  If Panel Error Remains, Panel Sensor May Need to be Replaced 

Solar Blocking 

Panel Sensor Fail 

3)  Tank Temperature Sensor Working Improperly 

Solar Blocking 

Tank Sol Sensor Fail 

4)  Solar Storage Tank Sensor Working Improperly 

Solar Blocking 

Storage Sensor Fail 

5)  Upper Tank Sensor Reached High Limit 

Solar Blocking 

High Temp Reached 

Table 5 – Fault Conditions 

Summary of Contents for 7100P-220

Page 1: ...lement for a list of tools and materials required in solar installations STEP 1 INSTALLATION OF THE SENSORS 1 Remove cover from tank sensor opening to expose the stud Tt Remove the existing clip and nut See Figure 1 2 Attach the tank sensor grey wire provided in this kit to the stud using the existing clip and nut See Figure 2 3 Use a drill with bit to drill a hole in the center of the tank sensor...

Page 2: ...eed the solar connector sensor wires through a knockout on the right side of the electronics cabinet 11 Connect the panel sensor wires to the SOLAR SENSOR terminals on the customer connection board NHX Models ONLY 1 Connect the NHX pump power leads to the NHX PUMP J3 terminals on the customer connection board See Figure 7 2 Connect the wires from the top sensor of the solar storage tank to the Ts ...

Page 3: ...nnect the flow meter wire from the customer connection board and install the flow meter as described in the included instruction sheet on the collector supply line pipe running from the Versa Hydro to the solar collector 5 After the flow meter is properly installed feed the flow meter wire through the knockout and reconnect to the customer connection board 6 See Figure 9 for an example of complete...

Page 4: ...e and cold water inlet of the appliance 3 Gas line must be rated to the maximum capacity of the unit Unit must have 10 feet of pipe after gas regulator 4 All circulators shall have an integral flow check 5 An ASSE 1017 mixing valve is required per SRCC OG 300 6 The flow meter must be properly supported and installed no more than one 1 foot from the Versa Hydro NOTE This drawing is meant to show sy...

Page 5: ...meters of straight pipe must be installed upstream of all circulators 6 Make sure tank is fully purged of air before power is turned on to the backup heat source 7 Circulators shown in the above hydronic piping should have an integral flow check or alternately use a stock pump with an external spring type check valve Due to extreme temperatures circulators with integral flow checks are not to be u...

Page 6: ...r inlet of the appliance 3 Gas line must be rated to the maximum capacity of the unit Unit must have 10 feet of pipe after gas regulator 4 All circulators shall have an integral flow check 5 An ASSE 1017 mixing valve is required per SRCC OG 300 6 The flow meter must be properly supported and installed no more than one 1 foot from the Versa Hydro NOTE This drawing is meant to show system piping con...

Page 7: ...low check remove it 8 Non vertical drain back solar system piping should pitch per foot to facilitate draining 9 No check valves are allowed within the solar loop 10 Solar pumps must be installed 3 below the drain back tank 11 The drain back tank must be properly supported 12 The flow meter must be properly supported and installed no more than one 1 foot from the Versa Hydro STEP 4 PROGRAMMING THE...

Page 8: ... Volts Range 1 to 10 Volts Table 3 Solar System Parameters STEP 5 SOLAR STATUS MENU The controller also has the ability to review solar system status To access solar status screens press twice Once the first value is displayed press the or keys to access additional information At any point you may press RESET to exit the solar status screens SCREEN DESCRIPTION 0 SOLAR SOLAR 0 FUEL This screen disp...

Reviews: