COMBITEST422
EN - 41
Fig. 20: Connection for a 400V + N (no PE) three-phase system by means of single cables
and remote switch probe
Fig. 21: Connection for a 400V + PE (no N) system with cables and remote switch probe
1. Press the
MENU
key, move the cursor to
RCD
in the
main menu by means of the arrow keys (
,
) and
confirm with
ENTER
. Subsequently, the instrument
displays a screen similar to the one reported here to the
side.
Select
“UK” as a country (see § 5.1.2), the options “TN,
TN or IT”, “25 or 50V”, “50Hz or 60Hz” and the reference
voltage in the general settings of the instrument (see §
5.1.3).
R C D
15/10
– 18:04
TT
T
Ut
=
=
- - -
- - -
ms
V
FREQ. = 0.00Hz
VL-PE=0V
VL-N=0V
X1
30mA
+
MODE
I
n
Type
Ut
2. Use the
,
keys to select the parameter to be modified, and the
,
keys to
modify the parameter value:
➢
MODE
→
The virtual key allows setting the measuring mode of the instrument,
which may be:
AUTO, x½, x1, x5,
➢
I
n
→
The virtual key allows setting the n
ominal value of the RCD’s tripping current,
which may be:
6mA, 10mA, 30mA, 100mA, 300mA, 500mA, 650mA, 1000mA
➢
Type
→
The virtual key enables the selection of the RCD type, which may be:
AC
(
), ACS (
S), A (
), AS (
S)
,
B
(
) with polarity positive (+) or negative (-)
➢
Ut
→
The virtual key allows setting the possible visualization of the contact voltage
value at the end of measurement. Options:
Ut
or
NoUt