Chapter 6 Function Introduction
Shenzhen Hpmont Technology Co., Ltd.
-30-
HD3Z Series User Manual V1.2
Ref. Code
Function Description
Setting Range [Default]
F00.22
Dormancy wake up time
0.0 - 6000.0 [1.0s]
F00.24
Dormancy delay time
0.0 - 6000.0 [1.0s]
F00.25
Dormancy frequency
0.00 - Upper limit frequency
[0.00Hz]
F00.21 - F00.25 is used for dormancy and wake up.
•
If HD3Z is in dormant status and receive run command, and setting frequency ≥ F00.25, when F00.22
(dormancy wake up time) is finished, HD3Z wakes up from dormancy status and starts running;
•
During running, and setting frequency < F00.25, when F00.24 (dormancy delay time) is finished, HD3Z
enters dormancy status
displays on keypad) and stop running.
F00.26
Action selection of HD3Z at zero-speed
00 - 12 [11]
Unit: Action selection of zero-speed under V/f control
0: Do not process.
1: HD3Z does not output.
2: HD3Z runs at DC brake.
Ten: Unused
F00.27
Command channel binding frequency channel
000 - ddd [000]
Valid only for main frequency. When command channel is bound to frequency channel, frequnecy channel
set by F00.10 will be invalid during this binding.
Unit: Keypad binds to frequency channel
Ten: Terminal binds to frequency channel
Hundred: SCI binds to frequency channel
•
0: No binding.
•
1: Keypad digital setting.
•
2: Terminal digital setting.
•
3: SCI setting.
•
5: Terminal pulse setting.
•
7: AI1.
•
8: AI2.
•
C: PID.
•
D: Multi-speed.
F00.28
Function of STOP button
0,1 [0]
0: Valid in keypad control mode only.
1: Valid in all control modes.
RUN