Chapter 6 Function Introduction
Shenzhen Hpmont Technology Co., Ltd.
-28-
HD3Z Series User Manual V1.2
6.2
General Parameters
6.2.1
F00: Basic Parameters
Ref. Code
Function Description
Setting Range [Default]
F00.06
Max. output frequency of HD3Z
50.00 - 400.00 [50.00Hz]
Defines the max. frequency that HD3Z is allowed to output.
F00.08
Upper limit of running frequency
0.00 - F00.06 [50.00Hz]
F00.07 = 0, the upper limit frequency is set by F00.08.
F00.09
Lower limit of running frequency
0.00 - F00.08 [0.00Hz]
F00.10
Frequency setting channels
0 - 7 [0]
0: Keypad. Change the value by pressing
, button on keypad. Initial value is set by F00.13.
1: Terminal. Change the value by using UP/DN. Initial value is set by F00.13.
2: SCI communication. Change the setting frequency by SCI command.
•
The initial value of the SCI frequency is 0.
3: Analogue. Set by analogue input voltage, refer to group F16.
•
Refer to group F16.
•
Refer to group F05 for the corresponding relationship between the analogue value and the running
frequency of HD3Z.
4: DI pulse.
•
Refer to group F05 for the corresponding relationship between the pulse terminal frequency and the
running frequency of HD3Z.
6: AI1.
7: AI2.
F00.11
Command setting channel
0 - 2 [0]
0: Keypad. Start and stop HD3Z by pressing
,
,
.
1: Terminal. Start and stop by using corresponding external terminals.
•
DI treminal is set as FWD (DI = 2), REV (DI = 3), JOGF1 (DI = 20), JOGR1 (DI = 21), JOGF2 (DI = 22) and
JOGR2 (DI = 23), refer to group F15.
2: SCI. Start and stop by SCI port according to communication protocol.
F00.12
M key function
0 - 2 [2]
0: Switch running direction. Switch running direction by
button.
•
F00.11 = 0, it is valid. Do not save when power is off.
•
Direction can be switched only when keypad displays status parameter.
1: Switch local and remote control. Switch the local and remote control by
The logic is shown in below
figure.
•
F00.11 = 0: LOCAL.
•
F00.11 =1,2: REMOTE.
•
Channel priority: Local / Remote > command channel set by DI terminal (No.9, 10, 11 function) >
command set by F00.11.
2: M key invalid.
Operate mode
Terminal
Keypad
Keypad
Terminal
Terminal
Comm-
unicaiton
Comm-
unicaiton
Running command channel
Determined by
both F00.11 and
DI terminal
SCI comm-
unicaiton