MVK-EIMC-EIHC KITS 

(UNASSEMBLED) 

INSTRUCTIONS 

 

Page 1 

H

ONEYWELL

   

APPLICATION 

   

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

These ignition modules provide ignition sequence, flame 
monitoring and safety shutoff for intermittent pilot 

central furnaces and heating appliances.  S8600 

module provides up to 1.0 A pilot and 1.0 A main valve 
current rating.  Minimum ambient temperature rating is  

-40 F [-40C]. Maximum ambient rating is +175 F [+79 C] 
for S8600 used with 1.0 A or less main valve. 

 
 
 
 

IMPORTANT: INSTALLATION 

 

  
 

We recommend that our products 
be installed and serviced by 

professionals who are certified in 
the U.S. by NFI (National Fireplace 
Institute) or in Canada by WETT 

(Wood Energy Technical Training).   

Installer must follow all instructions 

carefully to ensure proper 
performance and safety. 

 

 
 

 

 
 

 

 
 

 

 
 

 

 
 

 

 
 

WHEN INSTALLING THIS IGNITION SYSTEM… 
  
1. Read these instructions carefully.  Failure to follow 

them could damage the components or cause a 

hazardous condition. 
  2. Check the ratings given in the instructions and on 

the components to make sure they are suitable for your 

application. 
  3. Installer must be a trained, experienced service 

technician. 

  4. After installation is complete, check out component 
operation as provided in these instructions. 

  5. Fireplace installation- do NOT close doors to     

fireplace at ant time during use- will result in damage to 
components. 

WARNING 

FIRE OR EXPLOSION HAZARD. 

CAN CAUSE SERIOUS INJURY OR DEATH. 
1. The ignition module can malfunction if it gets wet, 

leading to accumulation of explosive gas. 

   

y

  Never install where water can flood, drip or             

condense on module. 

   

y

  Never try to use a module that has been wet-

replace it. 
2.  Liquefied petroleum (LP) gas is heavier than air 

and will not vent upward naturally. 

   

y

  Do not light pilot or operate electric switches, 

lights, or appliances until you are sure the appliance 

area is free of gas. 

 

MOUNT IGNITION MODULE 

   Select a location close enough to the burner 
to allow a short (3ft), direct cable route to the 

igniter.  Ambient temperature at the module 

must be within the range listed under 
APPLICATION.  The module must be protected 

from water, moisture, corrosive chemicals and 

excessive dust and grease. 
  We recommend mounting the module with the 

terminals down to protect them from dripping 

water and dust. It can also be mounted with the 
terminals on either side.  DO NOT MOUNT with 

terminals pointing up.  Fasten securely with four 
No. 6-32 machine or No.8 sheet metal screws. 

MOUNT THE SYSTEM CONTROLS 

  Mount any required controls, such as the gas 
control, spark igniter, flame sensor, thermostat, 

limit and transformer according to 

manufacturer’s instructions. Seal all electrical 
connections (terminals, connectors, & wire nuts) 
with electrical silicone to prevent shorting. 

 

 
 

 
 

 

 
 

 

 

 

CAUTION 

1. Disconnect power supply before beginning wiring 

to prevent electrical shock or equipment damage. 
2.  If a new gas control is to be installed, turn off gas 

supply before starting installation.  Conduct Gas 

Leak Test according to gas control manufacturer’s 
instructions after the gas control is installed. 

3. If module must be mounted near moisture or 
water, provide suitable waterproof enclosure. 

CAUTION

1. Check the wiring diagram furnished by the 

appliance manufacturer, for circuits differing 

from the wiring hookups shown.  
2.  Disconnect the power supply before making 

wiring connections to prevent electrical shock or 
equipment damage. 

 