Overview 13
Overview
Installation considerations
CAUTION:
All plumbing to and from the HP POD 20c must be completed by a licensed plumber.
All wiring in and around the HP POD 20c must be completed by a licensed electrician. Failure to
comply with these instructions can impact your warranty and/or result in equipment damage.
(Optional) Fire suppression system
CAUTION:
The POD fire suppression system is manufacturer designed, engineered, and
installed to comply with national standards. However, HP does not certify that the installed fire
suppression system meets all local jurisdictional requirements. Compliance with local codes is
your responsibility, and includes specific local requirements for initial and periodic inspections,
certifications, and maintenance.
Any additional local requirements are not covered as part of the option price or basic installation
and deployment services, unless specifically included in an executed Statement of Work.
WARNING:
Fire suppression agents include a pre-discharge warning and evacuating system. In
the event of a fire, all protected space must be evacuated as soon as possible.
IMPORTANT:
The fire suppression abort button is located next to the ECS panel and can be
pressed to interrupt the 30-second fire suppression agent release delay for an additional 30
seconds. This button interrupts the countdown, but does not reset the 30-second fire suppression
agent release delay. The fire suppression agent release countdown will continue when the abort
button is released until the time is exhausted and the fire suppression agent is released.
The fire suppression system contains conventional fire alarm control circuits and includes features required
for single or dual-hazard suppression release applications, including a low-toxicity agent. In the event of fire
suppression release, the suppression tanks must be refilled by a certified technician.