Periodic maintenance 68
Component to be inspected
Task
Frequency
Capable Party
EPO System Test
EPO NON-FUNCTIONAL TEST
Mode Key Switch Test - rotate
keyed switch through all modes.
ARMED MODE - Verify:
•
Power Indicator - White
•
Armed Light - White
BYPASS MODE - Verify
•
Bypass Light - Green
TEST MODE - Verify:
•
Test Light - Amber
Press EPO button (each in
succession) and thermal trip to
verify:
•
Reset Light - White
•
Audible alarm
•
Visual lamp indicator
Replace light upon failure
Annually
Qualified personnel
Emergency Lighting
Verify emergency lighting is
visible when all lighting is off and
the POD doors are shut.
Every 2 years
Qualified personnel
Exit signs
Visually inspect exit signs for
damage. Replace as necessary.
Every 2 years
Qualified personnel
Emergency egress
Personnel door emergency egress
panic bars. (Visual and
operational inspection.)
Every 2 years
Qualified personnel
Access control
Component to be inspected
Task
Frequency
Capable Party
System functional test
Visual inspection and operational
test of door access contact
switches
Annually
Qualified personnel
—
Visual inspection and operational
test of the following:
•
Door access card readers
•
Electric strikes
•
Door release switches at each
personnel door and/or in
each personnel door panic
bar
Annually
Qualified personnel
Third-party components
All maintenance for third-party equipment will be defined by the manufacturer of the equipment. HP will, with
a defined and signed SOW, conduct all maintenance as identified by the original manufacturer.
Examples of external third party components that HP will conduct all manufacturer specified maintenance
with a signed SOW includes:
•
External UPS equipment