Table 7 Example of Rack Load Calculations
BTU/hour
Total Volt-amps (VA)
Weight
Height (U)
Quantity
Component
Maximum
Heat
Dissipation
Typical
Heat
Dissipation
Maximum
Power
Consumption
Typical
Power
Consumption
(kg)
(lbs)
4265
2763
1250
810
122
270
10
1
c7000
enclosure
3139
3139
920
920
11
25
10
4
BL460c Gen8
Server Blade
2422
1535
710
450
17
38
3.47
2
D3700 SAS
disk enclosure,
containing 25
HDDs with
300GB, 6 GB
SAS protocol
per HDD
696
696
204
204
18
41
2
2
Rack-mounted
System
Console
68
68
20
20
3
6
1
2
Maintenance
switch
-
-
-
-
8
19
1
1
CLIM patch
panel
-
-
-
-
153
338
42
1
Rack
(single-phase)
11998
9088
3514
2664
356
792
-
-
Total
For a total thermal load for a system with multiple racks, add the heat outputs for all the racks in
the system.