NS7 Enclosure Power Loads
The total power and current load for a rack depends on the number and type of enclosures
installed in it. Therefore, the total load is the sum of the loads for all installed enclosures.
In normal operation, the AC power is split equally between the power feeds on the two sides (left
and right) of the rack. However, if AC power fails on one side of the rack, the power feed(s) on
the remaining side must carry the power for all enclosures in that rack.
NOTE:
For NS7 CG X2 system specifications, see
“System Installation Specifications for NS7
.
Power and current specifications for each type of enclosure are:
Maximum Power
Consumption (VA)
2
Typical Power
Consumption (VA)
1
AC Power Lines per
Enclosure
Enclosure Type
Products used by NS7 X1
AC systems
230
230
-
BL460c Gen8 CPU
(64 GB RAM)
260
260
-
BL460c Gen8 CPU
(128 GB RAM)
290
290
-
BL460c Gen8 CPU
(192 GB RAM)
Products used by NS7 X2
AC systems
300
300
-
BL460c Gen9 CPU
(64 GB RAM)
315
315
-
BL460c Gen9 CPU
(128 GB RAM)
330
330
-
BL460c Gen9 CPU
(192 GB RAM)
Common products used by
NS7 X1 and NS7 X2 AC
systems
:
1250
810
6
c7000 enclosure
234
207
2
FDR IB ADI switch (for
NSADI)
234
207
2
FDR IB switches expansion
234
207
2
FDR IB cluster switch (for
NonStop X Cluster Solution)
160
130
2
Gen8 Storage CLIM
156
126
2
Gen8 Networking CLIM,
4C/1C (IP or Telco)
158
128
2
Gen8 Networking CLIM,
3C/2F (IP or Telco)
190
140
2
Gen9 Storage CLIM
48
NS7 System Installation Specifications