Table 1 North America/Japan Single-Phase Power Specifications
Modular PDU 1-phase
iPDU 1-phase
R5000 1-phase UPS
24 A
24 A
4500 W
Output Load
200 – 240 V
200 – 208 V
200 – 208 V
Input Voltage
NEMA L6-30P
NEMA L6-30P
NEMA L6-30P
Input Connector
N/A
N/A
200 – 208 V
Output Voltage
4 x C19
6 x C19
1 x L6-30R
Output Connectors
(28 x C13)
(20 x C13)
4 x C19
4 x C13
UPS outputs are connected to the compatible PDU inputs.
Notes
Table 2 North America/Japan Three-Phase Power Specifications
Modular PDU 3-phase
iPDU 3-phase
R12000 3-phase UPS
24 A
24 A
12 kW
Output Load
208V 3P Delta
208V 3P Delta
208V 3P Wye
Input Voltage
NEMA L15-30P
NEMA L15-30P
IEC309 560P9
Input Connector
N/A
N/A
208V 3P Delta
Output Voltage
6 x C19
6 x C19
2 x NEMA L15-30R
Output Connectors
(42 x C13)
(20 x C13)
UPS outputs are connected to the compatible PDU inputs.
Notes
AC Input Power for NS2300 Systems