Local display
This section contains operation information for the Hewlett Packard Enterprise G2 Series Metered, Switched,
and Metered & Switched Power Distribution Units.
OLED display
The OLED display provides information about the PDU and connected devices. The OLED window flashes
red when a critical alarm is active. Information about the basic configuration of some settings is available
through the OLED. Information about the full configuration of all settings is available through the remote
interfaces. The OLED display orientation can be changed using an OLED setting. The display can be rotated
0° and 180°.
The PDU has a three-button, graphical OLED interface panel. Use the buttons to change the screen display,
retrieve specific performance data, or change configuration values. The display view can also change
automatically. For example, the display changes to show active alarms as they occur, or particular displays
update due to a change in operating state.
The OLED display has two modes.
•
Screensaver mode
—Cycles through a set sequence of screens that display current PDU values. Current
values are refreshed every 10 seconds. The user cannot select a custom sequence of screens. The
screensaver displays automatically after 30 seconds of inactivity from the start-up screen, a menu, or a
submenu. Values are refreshed every five seconds.
•
Menu mode (OLED main menu)
—The settings that display under each high-level (main) menu depend
on your PDU model.
Menu mode
Button
When in menu mode
When in screensaver mode
Menu
Select from the four main menus.
Returns to the previous display screen before
entering the screensaver mode.
Scroll
Scrolls down through the list of menu items.
NOTE:
A highlighted menu item is ready to
be selected.
Returns to the previous display screen before
entering the screensaver mode.
Select
Opens the selected menu.
Returns to the previous display screen before
entering the screensaver mode.
LED unit status
The LED will change colors depending on the state of the PDU.
LED state
Description
Solid green
Normal operation
Solid red
Critical alarm
Solid orange
Warning Alarm
Blinking orange
Disconnected from network
Table Continued
94
Local display
Summary of Contents for HPE G2 Series
Page 16: ...3 Secure the tie wrap 16 Introduction ...
Page 20: ...20 Introduction ...
Page 23: ...Installing the PDU 23 ...
Page 25: ... Outlets facing the back of the rack Installing the PDU 25 ...
Page 26: ... Outlets facing the front of the rack 26 Installing the PDU ...
Page 28: ... Two mid height PDUs with outlets facing towards the center of the rack 28 Installing the PDU ...
Page 31: ... Half height Installing the PDU 31 ...
Page 35: ...Installing the PDU 35 ...
Page 37: ...2 Install the PDU in the rack frame Installing the PDU 37 ...
Page 47: ...3 Install the PDU Installing the PDU 47 ...
Page 49: ...Installing the PDU 49 ...
Page 64: ...Web menu options Menu Illustration Overview Alarms 64 Remote configuration ...
Page 65: ...Menu Illustration Help Table Continued Remote configuration 65 ...
Page 66: ...Menu Illustration Language 66 Remote configuration ...
Page 67: ...Menu Illustration Logs Remote configuration 67 ...
Page 68: ...Menu Illustration Settings 68 Remote configuration ...
Page 84: ...84 Remote configuration ...
Page 92: ...92 Configuring local access ...
Page 99: ...Local display 99 ...
Page 101: ...Local display 101 ...
Page 107: ...Local display 107 ...
Page 120: ...120 Connecting and configuring optional hardware ...