North America
Japan
Europe
Power Requirements
Voltage
120/208
200
380/415
Phase/Frequency
3W+G, 50-60 Hz
3W+G, 50-60 Hz
3W+N+G, 50-60 Hz
Power Distribution Unit
(PDU) required for all
GS1280 Models
3X-H7606-AA
3X-H7606-AA
3X-H7606-AB
Rated Current, each
PDU
24A
24A
24A
Typical Current for
Models 8 and16, each
PDU
18.5A
19A
10A
Typical Current for
Models 32 and 64, each
PDU
2.5A
2.5A
1.3A
Line Connection
Fixed cord & plug
Fixed cord & plug
Fixed cord & plug
Power Cord
5 x 10AWG
5 x 10AWG
5 x 4 mm2
Power Plug
L21-30P, Hubbell 2811
L21-30P, Hubbell 2811
IEC 32A, Hubbell 532P6W
Main Breaker
30A
30A
30A
Sub-breakers
3 x 20A(2p), 1 x 20A(3p)
3 x 20A(2p), 1 x 20A(3p)
3 x 15A(2p), 1 x 15A(3p)
Agency
UL Listed, cUL
UL Listed, cUL
TUV & CB report
Power Distribution Unit
(PDU) required for GS
1280 Models 32 and 64
3X-H7606-BA
3X-H7606-BA
3X-H7606-BB
Rated Current, each
PDU
48A
48A
25A
Typical Current, each
PDU
24A
25A
16A
Line Connection
Fixed cord & plug
Fixed cord & plug
Fixed cord & plug
Power Cord
5 x 8AWG
5 x 8AWG
5 x 4 mm2
Power Plug
IEC 60A, Hubbell 460P9W
IEC 60A, Hubbell 460P9W
IEC 32A, Hubbell 532P6W
Agency
UL Listed, cUL
UL Listed, cUL
TUV & CB report
QuickSpecs
HP AlphaServer GS1280 Systems
Technical Specifications
DA - 11921 Worldwide — Version 24 — July 23, 2007
Page 57